Laserfiche WebLink
UNDER DISPARSER CONTAINMENT it DC TESTING <br />Test Method By: O Manufacturer • Industry Standard o Professional Engr o Other (see below) <br />Test Method Uses: O Pressure O Vacuum • Hydrostatic o Other (see below) <br />Measuring Equipment Used: INCON TS -STS (Electronic Sump Test System) <br />Description <br />Disp # 112 <br />Disp # 3/4 <br />Disp # 5/6 <br />0:05 <br />UDC manufacturer <br />Bravo <br />Bravo <br />Bravo <br />9:51 AM <br />Initial Probe Reading <br />UDC material <br />Steel <br />Steel <br />Steel <br />11:22 AM <br />10:06 AM <br />UDC depth (inches) <br />9 <br />9 <br />9 <br />0.7888 <br />ion of UDC tested <br />Height from UDC bottom to highest <br />piping penetration <br />Bottom <br />Bottom <br />Bottom <br />Float <br />Float <br />Height from UDC bottom to lowest <br />electrical penetration <br />Bottom <br />Bottom <br />Bottom <br />No <br />Was sensor properly replaced after testing? <br />Condition of UDC prior to testing <br />Dry <br />Dry <br />Dry <br />Port <br />Depth of water level from UDC bottom (in.) <br />Comments: <br />6 <br />6 <br />6 <br />Wait time for water level to stabilize (hr:min) <br />0:05 <br />0:05 <br />0:05 <br />Test start time <br />11:07 AM <br />9:51 AM <br />9:51 AM <br />Initial Probe Reading <br />0.3312 <br />1.1956 <br />0.7886 <br />Test end time <br />11:22 AM <br />10:06 AM <br />10:06 AM <br />Final Probe Reading <br />0.3319 <br />1.1951 <br />0.7888 <br />ion of UDC tested <br />Entire <br />Entire <br />Entire <br />Type of shut -down present <br />Float <br />Float <br />Float <br />Was sensor removed for testing? <br />No <br />No <br />No <br />Was sensor properly replaced after testing? <br />Yes <br />Yes <br />Yes <br />Depth of water level from UDC bottom (in.) <br />Comments: <br />6 <br />6 <br />6 <br />Wait time for water level to stabilize (hr:min) <br />0:05 <br />0:05 <br />0:05 <br />Test start time <br />11:07 AM <br />9:51 AM <br />9:51 AM <br />Initial Probe Reading <br />0.3312 <br />1.1956 <br />0.7886 <br />Test end time <br />11:22 AM <br />10:06 AM <br />10:06 AM <br />Final Probe Reading <br />0.3319 <br />1.1951 <br />0.7888 <br />Test duration (hr:min) <br />0:15 <br />0:15 <br />0:15 <br />Change in water level (t 0.0000 inches) <br />0.0007 <br />-0.0005 <br />0.0002 <br />Pass/Fail threshold (10.0020 inches / } Hr.) <br />0.0020 <br />0.0020 <br />0.0020 <br />TEST RESULT <br />PASS <br />PASS <br />PASS <br />2006 Walton Engineering, Inc. <br />