Laserfiche WebLink
r <br /> A <br /> Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: QUIKSTOP #00125 <br /> Tank#: 3 Test Date: 4/14/98 <br /> Product: Unleaded Premium Work#: 460289 <br /> Test Method: Test Method: R.J.FTA <br /> Capacity: Manufacturer: Vaporless <br /> Diameter(in): L/D Model: LD2000 <br /> Product Level(in): L/D Serial#: 42530 <br /> Liquid Volume(Gals): Line Drain Back(ml): 160 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 15 <br /> Coef.of Expansion: Metering Pressure(psi): 12 <br /> Water On Tank(in): L/D Test Rate(gph): 2.4 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): <br /> Head Pressure(psi): <br /> Test Start Time: Test Method: TEI LT-3 <br /> Test End Time: Pump Brand: Red Jacket <br /> Test Rate(gph): <br /> System Type: Pressure <br /> Test Result: N/A <br /> Line Pressure(psi): 50 <br /> Line Start Time: 8:30:00 PM. <br /> Test Method: ULLAGE Line End Time: 8:45:00 PM <br /> UllageVolume(gals.): Line Start Level: 200 <br /> Ullage Test Time: Line End Level: 160 <br /> Ullage Vacuum(psi): Line Test Rate(gph): -0.04227213 <br /> Ullage Result: N/A Line Test Result: PASS <br /> 2 <br />