Laserfiche WebLink
Y <br /> Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: QUIKSTOP #00125 <br /> Tank#: 2 Test Date: 4/14/98 <br /> Product: Unleaded Regular Work#: 460289 <br /> Test Method: Test Method: R.J.FTA <br /> Capacity: Manufacturer: Vaporless <br /> Diameter(in): L/D Model: LD2000 <br /> Product Level(in): L/D Serial#: unreadable <br /> Liquid Volume(Gals): Line.Drain Back(ml): 120 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 15 <br /> Coef.of Expansion: Metering Pressure(psi): 13 <br /> Water On Tank(in): L/D Test Rate(gph): 2.1 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): <br /> Head Pressure(psi): <br /> Test Start Time: Test Method: TEI LT-3 <br /> Test End Time: Pump Brand: Red Jacket <br /> Test Rate(gph): <br /> System Type: Pressure <br /> Test Result: N/A <br /> Line Pressure(psi): 50 <br /> Line.Start Time: 8:00:00 PM <br /> Test Method: ULLAGE Line End Time: 8:15:00 PM <br /> U11ageVolume(gals.): Line Start Level: 250 <br /> Ullage Test Time: Line End Level: 210 <br /> Ullage Vacuum(psi): Line Test Rate(gph): -0.04227213 <br /> Ullage Result: N/A Line Test Result: PASS <br /> 3 <br />