Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: QUIKSTOP #00125 <br /> Tank#: 1 Test Date: 8/ 6/97 <br /> Product: Unleaded Plus Work#: 340449 <br /> Test Method: Test Method: R.J.FTA <br /> Capacity: Manufacturer: Vaporless <br /> Diameter(in): L/D Model: LD2000 <br /> Product Level(in): L/D Serial#: 12544 <br /> Liquid Volume(Gals): Line Drain Back(ml): 100 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 27 <br /> Coef.of Expansion: Metering Pressure(psi): 10 <br /> Water On Tank(in): L/D Test Rate(gph): 1.3 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): <br /> Head Pressure(psi): <br /> Test Start Time: Test Method: TEI LT-3 <br /> Test End Time: <br /> Pump Brand: Tokheim <br /> Test Rate(gph): <br /> System Type: Pressure <br /> Test Result: N/A <br /> Line Pressure(psi): 50 <br /> Line Start Time: 1:00:00.PM <br /> Test Method: ULLAGE Line End Time: 1:15:00 PM <br /> UllageVolume(gals.): Line Start Level: 190 <br /> Ullage Test Time: Line End Level: 160 _ <br /> Ullage Vacuum(psi): Line Test Rate(gph): -0.03 <br /> Ullage Result: N/A Line Test Result: PASS <br /> 2 <br />