Laserfiche WebLink
Triangle Environmental, Inc. <br /> T.E.I. SYSTEMS TANK,LINE AND LEAK DETECTOR TEST REPORT <br /> Facility: QUIKSTOP #00125 <br /> Tank#: 2 Test Date: 8/ 6/97 <br /> Product: Unleaded Regular Work#: 340449 <br /> 001100001000110M MENEEMEENEM <br /> Test Method: Test Method: R.J.FTA <br /> Capacity: Manufacturer: Vaporless <br /> Diameter(in): L/D Model: LD2000 <br /> Product Level(in): L/D Serial#: ILL. <br /> Liquid Volume(Gals): Line Drain Back(ml): 110 <br /> Liquid Percent(%): L/D Trip Time(sec): 2 <br /> Specific Gravity: Holding Pressure(psi): 28 <br /> Coef.of Expansion: Metering Pressure(psi): 10 <br /> Water On Tank(in): L/D Test Rate(gph): 1.0 <br /> Water In Tank(in): L/D Result: PASS <br /> Product Temp. (F): <br /> Head Pressure(psi): ig <br /> Test Start Time: ME <br /> Test Method: TEI LT-3 <br /> Test End Time: <br /> Pump Brand: Tokheim <br /> Test Rate(gph): <br /> System Type: Pressure <br /> Test Result: N/A <br /> Line Pressure(psi): 50 <br /> Line Start Time: 1:20:00.PM <br /> Test Method: ULLAGE Line End Time: 1:35:00 PM <br /> UllageVolume(gals.): Line Start Level: 130 <br /> Ullage Test Time: Line End Level: 100 - <br /> Ullage <br /> 00 -Ullage Vacuum(psi): Line Test Rate(gph): -0.03 <br /> Ullage Result: N/A Line Test Result: PASS <br /> 3 <br />