SWRCB, January 2002 <br />Page _5_ of _7_ <br />Test Method Developed By: ❑ UDC Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: INCON TS - STS <br />Equipment Resolution: 0.002" <br />UDC #1-2 UDC #3-4 <br />UDC # UDC# <br />UDC Manufacturer: BRAVO PAN BRAVO PAN <br />UDC Material: <br />STEEL <br />STEEL <br />UDC Depth: <br />11" <br />11" <br />Height from UDC Bottom to Top <br />of Highest Piping Penetration: <br />NIA <br />N/A <br />Height from UDC Bottom to <br />N/A <br />NIA <br />Lowest Electrical Penetration: <br />Condition of UDC prior to <br />GOOD <br />GOOD <br />testing: <br />Portion of UDC Tested <br />ABOVE <br />ABOVE <br />PENETRATION <br />PENETRATION <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />❑ Yes ❑ No ®NA <br />❑ Yes ❑ No ® NA <br />❑ Yes ❑ No ❑ NA []Yes ❑No ❑ NA <br />product and water)?* <br />Turbine shutdown response time <br />N/A <br />N/A <br />Is system programmed for fail- <br />❑Yes [INo ®NA <br />[:1 Yes ❑ No ®NA <br />El Yes ❑ No ElNA E3 Yes ElNo ElNA <br />safe shutdown?` <br />Was fail-safe verified to be <br />❑ Yes ❑ No ®NA <br />❑ Yes ❑ No ®NA <br />El Yes ❑ No ElNA ❑Yes [:1No [INA <br />o erational?# <br />Wait time between applying <br />pressure/vacuum/water and <br />15 MIN <br />15 MIN <br />starting test <br />Test Start Time: <br />9:00 AM <br />9:00 AM <br />Initial Reading (RI): <br />4.8977" <br />1.8727" <br />Test End Time: <br />9:15 AM <br />9:15 AM <br />Final Reading (RF): <br />4.8990" <br />1.4444" <br />Test Duration: <br />15 MIN <br />15 MIN <br />Change in Reading (RF -RI): <br />0.0013" <br />-0.4283 <br />Pass/Fail Threshold or Criteria: <br />+/- 0.002" <br />+/_ 0.002" <br />F.Tesi Result: <br />M Pass Q Fait <br />El Pass, ® Fail <br />❑ Pass ' ❑ Fail . ❑ .Pass ❑ Faa1=.: <br />Was sensor removed for testing? <br />®Yes ❑ No ❑ NA <br />Z Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br />Was sensor properly replaced and <br />laced <br />[_LYe s [INo El NA <br />® Yes ❑ No ❑ NA <br />[I Yes F1 No ❑ NA ❑ Yes ❑ No ❑ NA <br />verified functional after testin? <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />ABOVE IS THE LAST OF TWO BACK TO BACK 15 MINUTE TESTS. <br />SENSORS WERE NOT TESTED DUE TO ANNUAL MONITOR CERTIFICATION. <br />' If the entire depth of the UDC is not tested, specify how much was tested. If the answer to aM of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160) <br />