SWRCB,January 2002 Page of <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: D Tank Manufacturer X Industry Standard D Professional Engineer <br /> D Other(Spec) <br /> Test Method Used: ❑Pressure X Vacuum D Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Equipment Resolution: <br /> Tank#87 Tank#91/DSL Tank# Tank# <br /> Is Tank Exempt From Testing?' Yes X No Yes X No D Yes No ❑Yes No <br /> Tank Capacity: 12,000 12,000 <br /> Tank Material: FIBERGLASS FIBERGLASS <br /> Tank Manufacturer: TOTAL TOTAL <br /> CONTAINMENT CONTAINMENT <br /> Product Stored: — GAS GAS/DIESEL <br /> Wait time between applying <br /> pressure/vacuum/water and 5 MIN 5 MIN <br /> starting test: <br /> Test Start Time: 12PM 12PM <br /> Initial Reading(RI): 10PSI I OPSI <br /> Test End Time: IPM IPM <br /> Final Reading(RF): I OPSI I OPSI <br /> Test Duration: IHR 1HR <br /> Change in Reading(RF-RI): 0 0 <br /> Pass/Fail Threshold or Criteria: 0 0 <br /> © .ail!. <br /> Was sensor removed for testing? X Yes D No ❑NA X Yes No ❑NA Yes D No D NA D Yes ❑No ❑NA <br /> Was sensor properly replaced and <br /> verified functional after testing? X Yes ❑No ❑NA X Yes ❑No DNA Yes 11No ❑NA ❑Yes D No ❑NA <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> 'Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing, (California Code of Regulations,Title 23,Section 2637(a)(6)) <br />