SWRCB.January 2002 Page 7 of 7 <br /> Site: UPS <br /> 1532 N.Broadway <br /> Stockton,CA 95205 <br /> Date: May 8,2009 <br /> 9. SPILL/OVERFILL CONTAINMENT BOXES <br /> Facility is Not Equipped With Spill/Overfill Containment Boxes [ ] <br /> Spill/Overfill Containment Boxes are Present, but were Not Tested [ ] <br /> Test Method Developed By: [ ]Spill Bucket Manufacturer [X]Industry Standard [ ]Professional Engineer <br /> _ Other(Specify) <br /> Test Method Used: [ ]Pressure [ ]Vacuum [X]Hydrostatic <br /> [ j Other(Specify) <br /> Test Equipment Used: Caldwell Equipment Resolution: 1/32" <br /> O.P.W. S ill Box Spill Box Spill Box <br /> Bucket Diameter: 12 inch <br /> Bucket Depth: 13 inch <br /> Wait time between <br /> applying <br /> pressure/vacuum/water and <br /> starting test: <br /> Test Start Time: 9:15 a.m. <br /> Initial Reading(R1): 11-1/2 inch <br /> Test End Time: 10:15 a.m. <br /> Final Reading(Rf): 11-1/2 inch <br /> Test Duration: 1 hour <br /> Change in Reading(Rf-RI) -0- <br /> Pass/Fail Threshold or <br /> Criteria: <br /> Test Result: X Pass Fail Pass [ Fail Pass Fail Pass Fail <br /> Comments—(include information on repairs made prior to testing,and recommended follow-up for failed tests) <br />