Laserfiche WebLink
N <br />9� ain ill <br />6rii[kc atiB i Fac; <br />Page 2 <br />4. TANK ANNULAR TESTING <br />Is Tank Exempt From Testing?' <br />❑ Yes X No <br />l Yes ❑ No <br />❑ Yes No <br />Yes No <br />Tank Capacity: <br />553 gallons <br />Tank Material: <br />Fiberglass <br />Tank Manufacturer: <br />Owens-Corning <br />Product Stored: <br />Diesel <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 min. <br />Test Start Time: <br />10:30 am <br />Initial Reading (RI): <br />6.5" of VA <br />Test End Time: <br />11:30 am <br />Final Reading (RF): <br />6.5" of VA <br />Test Duration: <br />I hour <br />Change in Reading (RF -RI): <br />none <br />Pass/Fail Threshold or Criteria: <br />One hour, no loss <br />Test Result: <br />X Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ' ❑ Fail <br />Was sensor removed for testing? <br />X Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />❑ Yes ` No ❑ NA <br />❑ Yes EE No ❑ NA <br />Was sensor properly replaced and <br />verified functional after testing? 11 <br />X Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />❑ Yes -]No ❑ NA <br />1 <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br />containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br />testing. (California Code of Regulations, Title 23, Section 2637(a)(6)1 <br />I:\apps\JOBS\2007\S01289.KINGCA\SB989 KINGCA.doc <br />