0 *T.C-4 M. Ke 761M, rem <br />Ground Water Monitor, <br />0 Probe Detects Absence of Water; Alarm ••- <br />• <br />Probe Detects Hydrocarbon; Alarm Operator <br />Probe Detects Water; Alarm Operator <br />Probe Detects Hydrocarbon Vapor; Alarm Operator <br />* Start-up of a shutdown STP can only be accomplished when the associ- <br />ated alarm condition has been cleared. <br />09irsTAMT-1 . a * i s _* a 0 - <br />0 provides audible and visual alarm on-site via SOC Unit, and off-site via <br />HMC System. * <br />0 records appropriate alarm information in Alarm History. <br />Limb Alarm Condition Clears: <br />0 automatically eliminates alarm indication from visual display. <br />0 records appropriate information in Alarm History. <br />• LjQa-EdQrijX Alarm Condition u[s: <br />0 provides audible and visual alarm on-site via SOC Unit. <br />Non -Priority Alarm Condition LJQBjr_a: <br />0 automatically eliminates alarm indication from visual display. <br />• In General: <br />0 audible alarm silenced when operator acknowledges on SOC Unit. <br />0 alarm display clears automatically when condition no longer exists, un- <br />less alarm has not been acknowledged, in which case display will re- <br />main active until alarm is acknowledged. <br />* The SOC Unit immediately calls the HMC system when any priority <br />alarm occurs and clears (if an HMC System is used). <br />** See the following section for description of the Alarm History func- <br />tions and requirements. <br />