Laserfiche WebLink
a) The system is capable of performing precision line tests to the highest <br />value, frequency and reliability as specified by the US EPA regulations <br />and applicable Local Codes (whichever is more stringent). It also has third <br />party certification. <br />aire-mrsournme arna <br />Annual Precision Test <br />Monthly Precision Test <br />Regulatory Leak Test <br />CatastronWic Lite Lea- <br />(e.g., 0.1 gph leak rate) <br />(e.g., 0.2 gph leak rate) <br />(e.g., 3 gph leak rate) <br />(e.g., > 10 gph leak rate) <br />tt Attempt a line test after each dispensing cycle of the pump. Dispenser <br />request aborts this test. <br />13 Automatically shutdown the STP and alarm when a failed Regulatory <br />test (e.g., 3 gph) is confirmed. <br />Allow one manual retest of any product line which fails the Regulatory <br />Test as indicated above. Authorized service personnel will be able to <br />override this lockout function for maintenance and troubleshooting of <br />the equipment. <br />13 Capability to perform leak testing at the command of the operator. This <br />function is equivalent to the line test which occurs automatically after <br />each dispensing cycle. <br />. 0 .. .•- <br />Monthly <br />0 - <br />Monthly Line Test Required <br />Failed Monthly Line Test <br />Failed Regulatory Line Test <br />Catastrophic Line Leak <br />(25 days since last achieved) <br />(e.g., 0.2 gph leak rate) <br />(e.g., 3 gph leak rate) <br />gph leak rate) <br />I' •• -Detects Water; Alarm, •'•- <br />• <br />Probe Detects Hydrocarbon; Alarm Operator <br />Probe Detects Water; Alarm Operator <br />Probe Detects Hydrocarbon; <br />Alar <br />I <br />