Laserfiche WebLink
1V 36341 ,J <br />Test Method Developed By: <br />❑ Piping Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: <br />® Pressure <br />❑ Other (Specify) <br />❑ Vacuum ❑ Hydrostatic <br />Test Equipment Used: Test reducer boots, Nitrogen and gauges Equipment Resolution: 0.5% of span <br />Piping Material: <br />Piping Run # Supply <br />Piping Run # Return <br />Fiberglass <br />Fiberglass <br />Piping Manufacturer: <br />Ameron <br />Ameron <br />Piping Diameter: <br />3" <br />3" <br />Length of Piping Run: <br />100' <br />125' <br />Product Stored: <br />Diesel <br />Diesel <br />Method and location of <br />piping -run isolation: <br />Reducer Boots/Fittings <br />Reducer Boots/Fittings <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />10 minutes <br />10 minutes <br />Test Start Time: <br />11:00 am <br />11:00 am <br />Initial Reading (Ri): <br />5 psi <br />5 psi <br />Test End Time: <br />12:00 pm <br />12:00 pm <br />Final Reading (RF): <br />5 psi <br />5 psi <br />Test Duration: <br />1 hr. <br />1 hr. <br />Change in Reading (RF -RI): <br />none <br />none <br />Pass/Fail Threshold or <br />Criteria: <br />No detectable Loss <br />No detectable Loss <br />Test Result: <br />El Pass ❑ Fail <br />El Pass ❑ Fail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />