Laserfiche WebLink
INDIVIDUA NK/LINE/LEAK DETECTOR TEIVEPORT <br /> TEST DATE: 03/18/98 WORK ORDER NUMBER: 2203916 <br /> CLIENT: SHELL OIL COMPANY SITE: SHELL 204-4416-0806 <br /> MENEM <br /> Tank ID: 2 Material:Dw FIBERG Bottom to top fill in inches: 180.0 <br /> Product:REG uNLEAD Tank manifolded:NO Bottom to grade fill in inches: 188.0 <br /> Capacity in gallons: 14,976 Vent manifolded:NO Fill pipe length in inches: 66.0 <br /> Diameter in inches: 114.00 Vapor recovery manifolded:YES Fill pipe diameter in inches: 4.0 <br /> Length in inches: 342 Impact Valves Operational: Stage I vapor recovery: DUAL <br /> Tank age(years): Overfill protection: YES Stage II vapor recovery: ASSIST <br /> Fuel pure rating: Overspill protection: YES Installed: ATG <br /> COMMENTS CP installed on: <br /> Start m n in New/passed Failed/replaced New/passed Failed/replaced <br /> Dipped Water Level: L.D.#1 L.D.#1 L.D.#2 L.D.#2 <br /> Dipped Product Level: Make:VEEDERROOT <br /> Probe Water Level: Model: L.L.D. <br /> Ingress Detected: Water Bubble Ullage S/N:TLS350-PLLD <br /> Test time: Open time in sec: <br /> VacuTect Test Type: Holding psi: 23 <br /> VacuTect Probe Entry Point: Resiliancy cc: 150 <br /> Pressure Set Point: Test leak rate ml/m: 189.0 <br /> Tank water level in inches: Metering psi: 10 <br /> Water table depth in inches: Calib.leak in gph: 3.00 <br /> Determined by(method): Results: PAss <br /> Result: <br /> COMMENTS COMMENTS <br /> Material: Dw FIBERG <br /> Diameter(in): 2.0 <br /> Length(ft): 100.0 <br /> Test psi: <br /> Bleedback cc: <br /> Test time(min): <br /> Test 1:Start time: <br /> Finish psi: <br /> Vol change cc: <br /> Test 2:Start time: <br /> Finish psi: <br /> Vol change cc: <br /> Test 3:Start time: <br /> Finish psi: <br /> Vol change cc: <br /> Final gph: <br /> Result: <br /> Pump type: PRESSURE <br /> COMMENTS Pump make: FE PETRO <br /> 8900 SHOAL CREEK,BUILDING 200,AUSTIN,TEXAS 78757(512)451-6334 Printed 03/20/98 10:17 MSHAW <br />