Laserfiche WebLink
L-A <br />Page 7 of 9 <br />8. FILL RISER CONTAINMENT SUMP TESTING <br />Facility is Not Equipped With Fill Riser Containment Sumps <br />❑ <br />Fill Riser Containment Sumps are Present, but were Not Tested ❑ <br />Test Method Developed By: <br />❑ Sump Manufacturer <br />❑ Other (Specify) <br />® Industry Standard ❑ Professional Engineer <br />Test Method Used: <br />❑ Pressure <br />❑ Other (Specify) <br />❑ Vacuum <br />® Hydrostatic <br />Test Equipment Used: See attached testing procedures <br />Fill Sump # 87-1 <br />Fill Sump # 87-2 <br />Equipment Resolution: <br />Fill Sump # 91 Fill Sump # <br />Sump Diameter: <br />48" <br />48" <br />48" <br />Sump Depth: <br />59" <br />58" <br />55" <br />Height from Tank Top to Top of <br />Highest Piping Penetration: <br />18" <br />18" <br />18" <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />24" <br />24" <br />20" <br />Condition of sump prior to <br />testing: <br />Fair <br />Fair <br />Fair <br />Portion of Sump Tested <br />Above highest <br />penetration <br />Above highest <br />penetration <br />Above highest <br />penetration <br />Above highest <br />penetration <br />Sump Material & Manufacturer: <br />Fiberglass <br />Fiberglass <br />Fiberglass <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />30 minutes <br />30 minutes <br />30 minutes <br />30 minutes <br />Test Start Time: <br />10:03am <br />9:57am <br />9:57am <br />Initial Reading (Ri): <br />0.6249 <br />5.0946 <br />0.1189 <br />Test End Time: <br />10:18am <br />10:12am <br />10:12am <br />Final Reading (RF): <br />0.6246 <br />5.0949 <br />0.1187 <br />Test Duration: <br />15 min <br />15 min <br />15 min <br />15 min <br />Change in Reading (RF -RI): <br />0.00030 <br />0.00028 <br />0.00016 <br />Pass/Fail Threshold or Criteria: <br />0.002 <br />0.002 <br />0.002 <br />0.002 <br />Test Result: <br />Z Pass El Fail <br />Z Pass ®`Fail <br />® Pass ❑ Fail <br />O'Pass ❑ Fail <br />Is there a sensor in the sump? <br />® Yes ❑ No <br />® Yes ❑ No <br />® Yes ❑ No <br />® Yes ❑ No <br />Does the sensor alarm when <br />either product or water is <br />detected? <br />®Yes ❑ No ❑NA <br />®Yes [-]No ❑NA <br />®Yes ❑ No [:]NA <br />❑Yes ❑ No ®NA <br />Was sensor removed for testing? <br />®Yes [-]No ❑NA <br />®Yes ❑ No ❑NA <br />®Yes [-]No ❑NA <br />®Yes [-]No ❑NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />®Yes ❑ No RNA <br />®Yes ❑ No ❑NA <br />®Yes ❑ No ❑NA <br />®Yes ❑ No [INA <br />Comments - (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />