Laserfiche WebLink
r <br />Page 9 of 9 <br />9. SPILL/OVERFILL CONTAINMENT BOXES <br />Facility is Not Equipped With Spill/Overfill Containment Boxes ❑ <br />Spill/Overfill Containment Boxes are Present, but were Not Tested ❑ <br />Test Method Developed By: <br />❑ Spill Bucket Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: <br />❑ Pressure ❑ Vacuum ❑ Hydrostatic <br />® Other (Specify) 1 hour visual leak test <br />Test Equipment Used: See attached testing procedures <br />Equipment Resolution: <br />Bucket Diameter & Brand: <br />Spill Box # 87-1 Vapor Spill Box #87-2 <br />Vapor <br />12" 12" <br />moo= Elm= <br />Spill Box # 91 Vapor Spill Box # <br />12" <br />Bucket Depth: <br />14" 14" <br />14" <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />30 Minutes 30 Minutes <br />30 Minutes 30 Minutes <br />Test Start Time: <br />8:27am 8:27am <br />8:27am <br />Initial Reading (RI): <br />13" 131/4" <br />131/2" <br />Test End Time: <br />9:27am 9:27am <br />9:27am <br />Final Reading (RF): <br />13" 131/4" <br />13 'h" <br />Test Duration: <br />1 hour 1 hour <br />1 hour <br />Change in Reading (RF -RI): <br />0 0 <br />0 <br />Pass/Fail Threshold or <br />Criteria: <br />0 0 <br />0 <br />Test Result: <br />® Pass ❑ Fail ® Pass ❑ Fail - <br />—L E Pass ❑ Fail ❑ Pass ❑ Fail <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />