1. ONLY AUTHORIZED/TRAINED PERSONNEL MAY USE THE FUEL LOAD RACK SYSTEM. <br />2. OPEN THE MANWAY ON TOP OF THE TANKER, PART WAY, FOR PROPER VENTILATION. <br />3. STICK THE TANK TO DETERMINE THE AMOUNT OF FUEL THE TANKER COULD ACCEPT. <br />4. POSITION 5 GALLON BUCKET UNDER THE TANKER'S FUELING CONNECTION. REMOVE <br />THE DUST CAP FROM THE TANKER'S DRY DISCONNECT AND FROM THE HOSE END <br />THEN ATTACH THE HOSE. OPEN THE VALVE ON THE END OF THE HOSE. <br />5. ON THE TANKER, CLOSE VALVE #5 (GREEN HANDLE). CLOSED IS IN THE UP POSITION. <br />OPEN VALVE #4 (WHITE HANDLE). OPEN IS IN THE DOWN POSITION, AND CLOSE <br />VALVE #3(BLACK HANDLE). <br />6. SET THE METER ON THE LOAD RACK FOR DESIRED QUANTITY OF FUEL. (SEE <br />INSTRUCTIONS POSTED ON THE METER). <br />7. SET THE METER'S VALVE LEVER BY PULLING ARM BACK TOWARDS THE METER <br />(SPRING ACTION HANDLE MOUNTED ON LEFT SIDE OF METER). <br />8. TURN PUMP SWITCH ON TO ENERGIZE THE TURBINE PUMP. <br />9. SLOWL OPEN THE VALVE ADJACENT TO THE METER ON THE LOADING RACK. FUEL <br />IS NOW FLOWING INTO THE TANKER AT APPROXIMATELY 200 GALLONS PER MINUTE. <br />10.PERFORM DAILY PRE -CHECK OF HIGH LEVEL SENSOR IN THE TANKER <br />• AFTER 1 MINUTE OF FUELING, OPEN THE TANKER PRE -CHECK VALVE. THE <br />VALVE IS LOCATED IMMEDIATELY BELOW AND TO THE RIGHT WHERE THE FUEL <br />LINE ENTERS THE TANK. <br />• WAIT 10 SECONDS; THE METER SHOULD STOP! IF THE METER DOES NOT STOP, <br />THERE IS A MALFUNCTION IN THE SECONDARY SHUT-OFF. CONTACT YOUR <br />FOREMAN IMMEDIATELY. <br />• RESET THE PRE -CHECK VALVE TO CONTINUE FUELING. <br />11.ONCE FUELING IS COMPLETE, TURN THE TURBINE PUMP SWITCH OFF. <br />12.CLOSE VALVE ON THE LOADING RACK. <br />13.REMOVE LOADING RACK HOSE AND REPLACE COVERS ON BOTH DRY DISCONNECTS. <br />14.CLOSE THE MANWAY COVER ON TOP OF THE TANKER. <br />15.IN EVENT OF AN EMERGENCY, DEPRESS THE RED STOP BUTTON ON THE METER (FAR <br />RIGHT BUTTON). THE MAIN ELECTRICAL SHUT-OFF IS MOUNTED OUTSIDE, ON THE <br />EAST SIDE OF THE MAINTENANCE BUILDING APPROXIMATELY 3 FEET TO THE NORTH <br />OF THE MAINTENANCE SUPERINTENDENT'S OFFICE. THIS SHUT-OFF CONTROLS THE <br />FUEL ISLAND AND FUEL RACK. <br />GENERAL RULES <br />• THE LOAD RACK MUST BE MANNED AT ALL TIMES DURING THE FUELING PROCESS. <br />• HOUSEKEEPING IS A SIGNIFICANT ISSUE. EVERY EFFORT MUST BE MADE NOT TO DRIP <br />FUEL ONTO THE GROUND. ANY SPILLAGE MUST BE CLEANED IMMEDIATELY. <br />• ANY LEAKS DUE TO WORN GASKETS OR MECHANICAL FAILURE MUST BE REPORTED <br />IMMEDIATELY. <br />• NO SMOKING PERMITTED BY ANY INDIVIDUAL WITHIN 50 FEET OF THE TANKER EITHER <br />DURING FUELING OF THE TANKER OR WHILE FUELING EQUIPMENT IN THE YARD. <br />