Laserfiche WebLink
8. FILL BUCKET CONTAINMENT SUMP TESTING <br />Page of <br />Test Method Developed By: Sump Manufacturer X Industry Standard Professional Engineer <br />Other (Specify) <br />Test Method Uses: Pressure Vacuum X Hydrostatic <br />Other (Specify) <br />Measuring Equipment Used for Testing: INCON TS -STS V2.1 <br />Fill Sump # D Fill Fill Sump # Fill Sump # <br />Sump Diameter: 12" <br />Sump Depth: <br />16" <br />Height from Tank Top to <br />Highest Piping Penetration: <br />0" <br />Height from Tank Top to <br />Lowest Electrical Penetration: <br />N/A <br />Condition of sump prior to <br />testing: <br />Dry <br />Portion of Sump Tested <br />All <br />Sump Material: <br />Plastic <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />15 Min. <br />Test Start Time: <br />9:44 / 10:27 <br />Initial Reading (R,): <br />5.172 / 6.846 <br />Test End Time: <br />9:59 /10:42 <br />Final Reading (RF): <br />5.171 / 6.845 <br />Test Duration: <br />15 Min. <br />Change in Reading (RF -RI): <br />.001/.001 <br />Pass/Fail Threshold: <br />.002 <br />Test Result: <br />Pass <br />Is there a sensor in the sump? <br />No <br />Does the sensor alarm when <br />either product or water is <br />detected? <br />N/A <br />Was sensor removed for <br />testing? <br />N/A <br />Was sensor properly replaced <br />after testing? <br />N/A <br />Comments — (include information on repairs made to facilitate a passing test and indicate whether a <br />permit was obtained for the repairs) <br />All hydrostatic test performed twice to insure testing results <br />R.C.U.S.T.COM December 2001 <br />