Laserfiche WebLink
Page of <br />4. TANK ANNULAR TESTING <br />Test Method Developed By: X Tank Manufactum ❑ Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Uses: ❑ Pressure X Vacuum ❑ Hydrostatic <br />❑ Other (Spec) <br />Measuring Equipment Used for Testing: Liquid Filled Gauge 1% Dial Span Accuracy <br />Tank # 1 Tank # Tank # <br />Tank Capacity: 12,000 <br />Tank Material: Fiberglass/ Steel <br />Tank Manufacturer: Modern <br />Product Stored: Diesel <br />Wait time between applying <br />pressure/vacuum/water and starting 15 Min. <br />test: <br />Test Start Time: 10:15 <br />Initial Reading (RI): 10" Vacuum <br />Test End Time: 11:15 <br />Final Reading (RF): 10" Vacuum <br />Test Duration: I Hour <br />Change in Reading (RF -R,): 0 <br />Pass/Fail Threshold: 0 <br />Test Result: Pass <br />Was sensor removed for testing? Yes <br />Was sensor properly replaced after <br />testing? Yes <br />Comments — (include information on repairs made to facilitate a passing test and indicate whether a <br />permit was obtained for the repairs) <br />T), n it o T !ll -%7,R <br />