Laserfiche WebLink
Page of <br />5. SECONDARY PIPE TESTING <br />Test Method Developed By: X Piping IVufacturer ❑ Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Uses: X Pry ❑ Vacuum ❑ Hydrostatic <br />❑ Other (Spec) <br />Measuring Equipment Used for <br />Testing: Liquid <br />Piping Run # 1 <br />Fiberglass <br />Filled Gauge 1% Dial Span Accuracy <br />Piping Run # 2 Piping Run # <br />Fiberglass <br />Piping Material: <br />Piping Manufacturer: <br />Ameron <br />Ameron <br />Piping Diameter: <br />3" <br />4" <br />Length of Piping Run: <br />50' <br />20' <br />Product Stored: <br />Diesel <br />Diesel <br />Method and location of <br />piping -run isolation: <br />Ameron Isolation Boot <br />Ameron Isolation Boot <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />15 Min. <br />15 Min. <br />Test Start Time: <br />10:15 <br />10:15 <br />Initial Reading (RI): <br />5 P.S.I. <br />5 P.S.I. <br />Test End Time: <br />11:15 <br />11:15 <br />Final Reading (RF): <br />5 P.S.I. <br />5 P.S.I. <br />Test Duration: <br />1 Hour <br />1 Hour <br />Change in Reading (RF -RI): <br />0 <br />0 <br />Pass/Fail Threshold: <br />0 <br />0 <br />Test Result: <br />Pass <br />Pass <br />Comments — (include information on repairs made to facilitate a passing test and indicate whether a <br />permit was obtained for the repairs) <br />Note: Pressure testing of piping secondary containment systems should be performed at 5 PSI, <br />which is generally consistent with testing performed at time of installation. <br />n 11 Y 11 m nr%w,r r t _'1AA1 <br />