Laserfiche WebLink
11 <br />0 <br />Page 2 of 6 <br />4. TANK ANNULAR TESTING <br />Test Method Developed By: ❑ Tank Manufacturer X Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure X Vacuum ❑ Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used: Liquid Filled Gauge 1% Dial Span Accuracy Equipment Resolution: 30" <br />Tank # Diesel <br />Is Tank Exempt From Testing?' ❑ Yes X No <br />Tank Capacity: <br />20,000 <br />Tank Material: <br />steel <br />Tank Manufacturer: <br />joor <br />Product Stored: <br />diesel <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />15 Minutes <br />Test Start Time: <br />0800 <br />Initial Reading (RI <br />10" <br />Test End Time: <br />1000 <br />Final Reading (RF): <br />10" <br />Test Duration: <br />2 Hour <br />Change in Reading (RF -RI): <br />0" <br />Pass/Fail Threshold or Criteria: <br />0" <br />Test Result: <br />X Pass ❑ Fail <br />Was sensor removed for testing? <br />X Yes ❑ No ❑ NA <br />Was sensor properly replaced and <br />verified functional after testin ? <br />X Yes ❑ No ❑ NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br />containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br />