Page_of <br /> 4. TANK ANNULAR TESTING <br /> Test Method Developed By: ❑Tank Manufacturer ® Industry Standard ❑Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ®Vacuum ❑Hydrostatic <br /> ❑ Other(Specify) <br /> Test Equipment Used: DIGITAL MANOMETER Equipment Resolution: <br /> Tank#1171 Tank# Tank# Tank# <br /> Is Tank Exempt From Testing?' ❑Yes ®No ❑Yes ❑No ❑Yes ❑No ❑Yes ❑No <br /> Tank Capacity: 4010 GALLONS <br /> Tank Material: FIBER/STEEL <br /> Tank Manufacturer: MODERN <br /> WELDING <br /> Product Stored: RED DIESEL <br /> Wait time between applying <br /> pressure/vacuum/water and 15 MIN. <br /> starting test: <br /> Test Start Time: 9:15 AM <br /> Initial Reading(RI): 7 INCH HG <br /> Test End Time: 10:15 AM <br /> Final Reading(RF): 7 INCH HG <br /> Test Duration: 1 HOUR <br /> Change in Reading(RF-RI): 0 IN HG <br /> Pass/Fail Threshold or Criteria: 0 <br /> Test Result: ® Pass ❑ Fail ❑ Pass []Fail ❑ Pass ❑Fail ❑ Pass ❑ Fail <br /> Was sensor removed for testing? ®Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes❑No ❑NA ❑Yes ❑No ❑NA <br /> Was sensor properly replaced and ®Yes ❑No ❑NA ❑Yes ❑No ❑NA ❑Yes❑No ❑NA ❑Yes ❑No ❑NA <br /> verified functional after testing? <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> TANK 1171 ANNULAR PASSED REQUIRED VACUUM TEST.NO REPAIRS ARE NEEDED AT THE PRESENT TIME. <br /> ' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br /> containment,such as systems that are hydrostatically monitored or under constant vacuum,are exempt from periodic containment <br /> testing. {California Code of Regulations,Title 23,Section 2637(a)(6)) <br />