Laserfiche WebLink
f <br /> Page of_ <br /> 7. FILL RISER CONTAINMENT SUMP TESTING <br /> Facility is Not Equipped With Fill Riser Containment Sumps ❑ <br /> Fill Riser Containment Sumps are Present,but were Not Tested ❑ <br /> Test Method Developed By: ❑ Sump Manufacturer ®Industry Standard ❑Professional Engineer <br /> ❑ Other(Specify) <br /> Test Method Used: ❑Pressure ❑Vacuum ®Hydrostatic <br /> ❑ Other(Spec) <br /> Test Equipment Used: INCON TS-STS TEST UNIT Equipment Resolution: <br /> MENIMMEM <br /> Fill Sump#1171 Fill Sump# Fill Sump# Fill Sump# <br /> Sump Diameter: 44 INCHES <br /> Sump Depth: 80 INCHES <br /> Height from Tank Top to Top of 32 INCHES <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest 31 INCHES <br /> Electrical Penetration: <br /> Condition of sump prior to GOOD <br /> testing: <br /> Portion of Sump Tested 2 INCHES ABOVE <br /> SUMPS HIGHEST <br /> PIPING <br /> PENETRATION <br /> Sump Material: PLASTIC <br /> Wait time between applying 15 MIN. <br /> pressure/vacuum/water and <br /> starting test: <br /> Test Start Time: 10:06 AM 10:33 AM <br /> Initial Reading(Ri): 4.6017 4.8263 <br /> Test End Time: 10:21 AM 10:52 AM <br /> Final Reading(RF): 4.6031 4.8263 <br /> Test Duration: 15 MIN. 15 MIN. <br /> Change in Reading(RF-R,): .0014 .0000 <br /> Pass/Fail Threshold or Criteria: 0.002 0.002 0.002 0.002 0.002 0.002 0.002 0.002 <br /> Test Result: ® Pass ❑Fail ❑ Pass ❑Fail ❑ Pass ❑ Fail ❑ Pass ❑ Fail <br /> Is there a sensor in the sump? ®Yes ❑No ❑Yes ❑No ❑Yes ❑No ❑Yes ❑No <br /> Does the sensor alarm when ❑Yes ❑No ❑ <br /> either product or water is ®Yes ❑No ❑NA NA ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> detected? <br /> Was sensor removed for testing? ®Yes ❑No ❑NA ❑Yes ❑No ❑ ❑Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> NA <br /> Was sensor properly replaced and ®Yes ❑No ❑NA ❑Yes El No ❑ ❑Yes ❑No F1 NA ❑Yes ❑No ❑NA <br /> verified functional after testing? NA <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> FILL SUMP PASSED THE REQUIRED HYDROSTATIC TEST.NO REPAIR ARE NEEDED AT THE PRESENT TIME. <br /> i <br />