Laserfiche WebLink
6APPENDIX B - Page 13.3 <br />3. <br />The TLM <br />will be able to detect (in the tank integrity mode) a minimum <br />of a 0.20 gallon per hour leak while compensating for temperature <br />changes <br />within the tank with a probability of leak detection of 95 <br />percent <br />and probability of false alarms of 5 percent; <br />4. <br />The TLM <br />system will be Level TRU (Model No. 10600) by Environment and <br />Safety, <br />Inc., Veeder-Root TLS -350 with magnetostrictive probe, or <br />equal; <br />5. <br />Install <br />overspill protection device at the tank. The overspill <br />protection <br />device will be Skyway (Model No. 85000), Emco Wheaton <br />A1003, <br />or equal; <br />6. <br />Install <br />a pipeline leak detector and retrofit pressure piping system <br />with a <br />flow restriction device. The pipeline leak detector will be <br />LR 1000 <br />Leak Rater, Ronan X76 Line Leak Detector or equivalent. <br />GROUNDWATER <br />This facility is located within the San Joaquin Valley Groundwater Basin. <br />There is one groundwater well located approximately 300 feet northeast of the <br />facility. The local groundwater table elevation is unknown. <br />