SWRCB, January 2002 Page _2_ of —8- <br />4. TANK ANNULAR TESTING <br />Test Method Developed By: ❑ Tank Manufacturer N Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: ❑ Pressure N Vacuum ❑ Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: 0 — 30" VACUUM GAUGES <br />Equipment Resolution: + / - 0.002" <br />Tank # 87 MAIN <br />Tank # 87 SYPHON <br />Tank # 91 <br />Tank # <br />Is Tank Exempt From Testing?' <br />❑ Yes N No <br />❑ Yes N No <br />❑ Yes N No <br />❑ Yes ❑ No <br />Tank Capacity: <br />12,000 <br />12,000 <br />12,000 <br />Tank Material: <br />FIBERGLASS <br />FIBERGLASS <br />FIBERGLASS <br />Tank Manufacturer: <br />UNKNOWN <br />UNKNOWN <br />UNKNOWN <br />Product Stored: <br />87 <br />87 <br />91 <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />15 MIN <br />15 MIN <br />15 MIN <br />Test Start Time: <br />12:00 PM <br />12:20 PM <br />12:40 PM <br />Initial Reading (Rj): <br />10" <br />10" <br />10" <br />Test End Time: <br />1:00 PM <br />1:20 PM <br />1:40 PM <br />Final Reading (RF): <br />10" <br />10" <br />10" <br />Test Duration: <br />1 HR <br />1 HR <br />1 HR <br />Change in Reading (RF -R,): <br />0 <br />0 <br />0 <br />Pass/Fail Threshold or Criteria: <br />NO LOSS <br />NO LOSS <br />NO LOSS <br />NO LOSS <br />Test Results <br />N <br />Pass ❑ Fair <br />0 <br />Pass ❑ Fail <br />® Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Was sensor removed for testing? <br />❑ Yes N No ❑ NA <br />❑ Yes N No [--INA <br />❑Yes N No [:INA <br />❑Yes ❑ No [:INA <br />Was sensor properly replaced and <br />verified functional after testing? <br />❑Yes [:]No ®NA <br />❑Yes ❑ No ®NA <br />❑Yes ❑ No ®NA <br />❑Yes ❑ No ❑NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />SENSOR FUNCTIONALITY WAS NOT CONFIRMED. THIS PROCEDURE IS NOT A PART OF SB989 TESTING. <br />' Secondary containment systems where the continuous monitoring automatically monitors both the primary and secondary <br />containment, such as systems that are hydrostatically monitored or under constant vacuum, are exempt from periodic containment <br />testing. {California Code of Regulations, Title 23, Section 2637(a)(6)) <br />