Laserfiche WebLink
SWRCB, January 2002 <br />8. <br />0 0 Page _6_ of —8- <br />FILL RISER CONTAINMENT SUMP TESTING <br />Facility is Not Equipped With Fill Riser Containment Sumps ❑ <br />Fill Riser Containment Sumps are Present, but were Not Tested ❑ <br />Test Method Developed By: <br />❑ Sump Manufacturer <br />❑ Other (Spec) <br />® Industry Standard ❑ Professional Engineer <br />Test Method Used: <br />❑ Pressure <br />❑ Other (Spec) <br />❑ Vacuum <br />® Hydrostatic <br />Test Equipment Used: INCON SUMP <br />TESTER <br />Equipment Resolution: + / - 0.002" <br />EMFill <br />"SumDiameter: <br />Sump # 87 MAIN <br />Fill Sump # 87 <br />SYPHON <br />Fill Sump # 91 <br />Fill Sump # <br />48" <br />48" <br />48" <br />: <br />59" <br />60" <br />63" <br />Height from Tank Top to Top of <br />Highest Piping Penetration: <br />NIA <br />NIA <br />N/A <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />29" <br />31" <br />28" <br />Condition of sump prior to <br />testing: <br />FAIR <br />FAIR <br />FAIR <br />Portion of Sump Tested <br />2" ABOVE <br />SUMP COLLAR <br />2" ABOVE <br />SUMP COLLAR <br />2" ABOVE <br />SUMP COLLAR <br />Sump Material: <br />FIBERGLASS <br />FIBERGLASS <br />FIBERGLASS <br />Wait time between applying <br />pressure/vacuum/water and <br />starting test: <br />30 MIN <br />30 MIN <br />30 MIN <br />Test Start Time: <br />1:16 PM <br />1:16 PM <br />1:16 PM <br />Initial Reading (Rj): <br />2.0793" <br />2.0273" <br />1.9341 " <br />Test End Time: <br />1:31 PM <br />1:31 PM <br />1:31 PM <br />Final Reading (RF): <br />2.0787° <br />2.0278" <br />1.9347° <br />Test Duration: <br />15 MIN <br />15 MIN <br />15 MIN <br />Change in Reading (RF -RI): <br />- 0.0006" <br />0.0005" <br />0.0006" <br />Pass/Fail Threshold or Criteria: <br />+ / - 0.002" <br />+/-0.002" <br />+ / - 0.002" <br />+/-0.002" <br />Test Result: <br />Z Pass ❑ Fail <br />N' Pass ❑ Fail <br />® Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Is there a sensor in the sump? <br />® Yes ❑ No <br />® Yes ❑ No <br />® Yes ❑ No <br />❑ Yes ❑ No <br />Does the sensor alarm when <br />either product or water is <br />detected? <br />❑ Yes ❑ No ® NA <br />❑ Yes ❑ No ® NA <br />❑ Yes ❑ No ®NA <br />❑ Yes ❑ No ❑ NA <br />Was sensor removed for testing? <br />® Yes ❑ No ❑ NA <br />® Yes ❑ No ❑ NA <br />® Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />®yes ❑ No [:INA <br />® Yes ❑ No ❑ NA <br />I ®Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />ABOVE IS THE LAST OF TWO BACK TO BACK 15 MINUTE <br />TESTS <br />SENSOR FUNCTIONALITY WAS NOT CONFIRMED. THIS PROCEDURE IS NOT A PART OF SB989 TESTING. <br />