Laserfiche WebLink
bp <br /> 0 <br /> Line Leak Detector Test Data Sheet <br /> Station # Arco SS 5450 Date 7/26 2016 <br /> Address 1617 W. Fremont, Stockton, CA <br /> Test Information <br /> 1 2 3 45, <br /> Product 87 91 <br /> Manufacturer VR V <br /> Model 848480 848480 <br /> Full Operating Pressure(psi) 30 32 <br /> Line Bleed Back(ml) NA NA <br /> Trip Time(sec) <br /> NA NA <br /> Metering Pressure(psi) NA NA <br /> RE Holding Pressure (psi) 22 24 <br /> Test Leak Rate(ml/min)(gph) 189MI 1 9ml <br /> PASS or FAIL P <br /> Comments: <br /> This letter certifies that the annual leak detector tests were performed at the above referenced facility <br /> according to the equipment manufacturers procedures and limitations and the results as listed are to my <br /> knowledge true and correct. The mechanical leak test detector test pass/fail is determined using a, low <br /> flow threshold trip rate of 3 gph at 10 PSI. <br /> Inspected By: Contractor Gettler-Ryan Inc. <br /> Technician Elodio Sanchez Lic# <br /> Signature <br />