CCR,TITLE 23, DIVISION 3, CHAPTER 16, UNDERGROUND STORAGE TANK REGULATIONS CCR, TITLE 23, DLvISION 3, CHAPTER 16, UNDERGROUND STORAGE TANK REGUTATIONS <br /> (C) No valves or pumps are installed below grade in the suction line. percent of design operating pressure or pneumatically at 110 percent of design <br /> Only one check valve is located directly below and as close as operating pressure. If the calculated test pressure for pressurized piping is less <br /> practical to the suction pump; than 40 psi, 40 psi shall be used as the test pressure. The pressure shall be <br /> maintained for a minimum of 30 minutes and all joints shall be soap tested. A <br /> (D)An inspection method is provided which readily demonstra,.ts failed test,as evidenced by the presence of bubbles,shall require appropriate <br /> compliance with subdivisions(A)through (C) above. repairs and retesting. If there are no manufacturers guidelines,secondary <br /> containment systems shall be tested using an applicable method specified in an <br /> (b) All corrodible underground piping, if in direct contact with backfill material, industry code or engineering standard. Suction piping and gravity flow piping <br /> shall be protected against corrosion.Piping constructed of fiberglass-reinforced which cannot be isolated from the tank shall be tested after installation in <br /> plastic,steel with cathodic protection, or steel isolated from direct contact with conjunction with an overfilled volumetric tank integrity test,or other test <br /> backfill, fulfills this corrosion protection requirement. Cathodic protection shall method meeting the requirements of section 2643(0,if approved by the local <br /> meet the requirements of section 2635(a)(2). agency. <br /> (c) Underground primary piping shall meet all of the following requirements: (f) Underground piping with secondary containment shall be equipped and <br /> monitored as follows: <br /> (1) Primary piping in contact with hazardous substances under normal <br /> operating conditions shall be installed inside a secondary containment (1) The secondary containment system shall be equipped with a <br /> system which may be a secondary pipe,vault,or a lined trench. All continuous monitoring system which meets the requirements of <br /> secondary containment systems shall be sloped so that all releases will section 2643(f) and which is connected to an audible and visual alarm <br /> flow to a collection sump located at the low point of the underground system. <br /> piping. <br /> (2) Automatic line leak detectors shall be installed on underground <br /> (2) Primary piping and secondary containment systems shall be installed pressurized piping and shall be capable of detecting a 3-gallon per <br /> In accordance with an industry code of practice developed in hour leak rate at 10 psi within 1 hour with a probability of detection <br /> accordance with voluntary consensus standards. The owner or of at least 95 percent and a probability of false alarm no greater than 5 <br /> operator shall certify that the piping was installed in accordance with percent. Compliance with these standards shall be certified in <br /> the above requirements of section 2635(d). The certification shall be accordance with section 2643(17 of Article 4. <br /> made on the"Certification of Compliance for Underground Storage <br /> Tank Installation Form C" (see Appendix V). (3) Other monitoring methods may be used in lieu of the requirement in <br /> subdivision(2) if it is demonstrated to the satisfaction of the local <br /> (d) Lined trench systems used as part of a secondary containment system shall be agency that the alternate method is as effective as the methods <br /> designed and constructed according to a code of practice or engineering otherwise required by this section. A continuous monitoring system <br /> standard approved by a state registered professional engineer. The following as described in subdivision (1),which shuts down the pump in <br /> requirements shall also apply: addition to:activating the alarm system,satisfies the automatic line leak <br /> detector requirement of subdivision(2). <br /> (1) All trench materials shall be compatible with the substance stored and <br /> evaluated by an independent testing organization for their (4) Monitoring shall be conducted on all underground pressurized piping <br /> compatibility or adequacy of the trench design,construction, and with secondary containment at least annually at a pressure designated <br /> application. by the equipment manufacturer,provided that the method is capable <br /> of detecting a minimum release equivalent to 0.1 gallon per hour <br /> (2) The trench shall be covered and capable of supporting any expected defined at 1.50 percent of the normal operating pressure of the <br /> vehicular traffic. product piping system at the test pressure with at least a 95 percent <br /> probability of detection and not more than a 5 percent probability of <br /> (e) All new primary piping and secondary containment systems shall be tested for false alarm. This requirement is waived if the criteria in subsection(g) <br /> tightness after installation in accordance with manufacturer's guidelines. of this section are met. <br /> Primary pressurized piping shall be tested for tightness hydrostatically at 150 <br /> 3-17 3-18 <br />