7. UNDER -DISPENSER CONTAINMENT (UDC) TESTING <br />Test Method Developed By: ❑ UDC Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Incon Sump <br />Tester Equipment Resolution: +/- 0.002" <br />r <br />UDC # 1/2 UDC # 3/4 UDC # 5/6 UDC # 7/8 x <br />UDC Manufacturer: <br />OPW OPW OPW OPW <br />UDC Material: <br />Fiberglass Fiberglass <br />Fiberglass <br />Fiberglass <br />UDC Depth: <br />31" 31" <br />31" <br />31" <br />Height from UDC Bottom to Top <br />21„ 22" <br />21" <br />20" <br />of Highest Pi ,in Penetration: <br />Height from UDC Bottom to <br />6" 6" <br />8" <br />8" <br />Lowest Electrical Penetration: <br />Condition of UDC prior to <br />Good Good <br />Good <br />Good <br />testing: <br />Portion of UDC Tested <br />2" above piping 2" above piping <br />2" above piping <br />2" above piping <br />Does turbine shut down when <br />F <br />UDC sensor detects liquid (both <br />❑ Yes ❑ No ® NA ❑ Yes ❑ No ® NA <br />❑ Yes ❑ No ® NA <br />❑ Yes ❑ No ® NA <br />product and water)?* <br />' <br />Turbine shutdown response time <br />N/A N/A <br />N/A <br />N/A <br />Is system programmed for fail- <br />❑ Yes ❑ No ® NA ❑ Yes ❑ No ® NA <br />❑ Yes ❑ No ® NA <br />❑ Yes ❑ No ® NA <br />safe shutdown?` <br />Was fail-safe verified to be <br />❑ Yes ❑ No ® NA ❑ Yes ❑ No ® NA <br />❑ Yes ❑ No ® NA <br />❑ Yes ❑ No ® NA <br />operational?* <br />Wait time between applying <br />pressure/vacuum/water and <br />30 minutes 30 minutes <br />30 minutes <br />30 minutes <br />starting : test <br />Test Start Time: <br />4:11 pin 4:11 pm <br />1:04 pm <br />4:11 pm <br />Initial Reading (Ri): <br />2.6825 0.1979 <br />3.4624 <br />7.2177 <br />Test End Time: <br />4:26 pm 4:26 pm <br />1:19 pm <br />4:27 pm <br />Final Reading (RF): <br />2.6527 1.5836 <br />3.4624 <br />7.2178 <br />Test Duration: <br />15 min. 15 min. <br />15 min. <br />16 min. <br />Change in Reading (RF -RI): <br />0.0298 1.7815 <br />None <br />0.0001 <br />Pass/Fail Threshold or Criteria: <br />+/-0.002" +/- 0.002" <br />+/- 0.002" <br />+/-0.002" <br />Test Result: <br />❑ Pass El Fail ❑ Pass El Fail <br />® Pass ❑ Fail <br />M Pass ❑ Fail <br />Was sensor removed for testing? <br />® Yes ❑ No ❑ NA ® Yes ❑ No ❑ NA <br />® Yes ❑ No ❑ NA <br />® Yes ❑ No ❑ NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />® Yes ElNo ❑ NA ® Yes ElNo ❑ NA <br />N Yes ❑ No ❑ NA <br />® Yes ❑ No ElNA <br />5 <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />"Sensor functionality was not confirmed. This procedure is not part of the Secondary Containment testing scope of work". <br />1/2 & 3/4, Failed due to torn penetration conduits. <br />a <br />' If the entire depth of the UDC is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br />asterisk(*) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160) <br />