6. PIPING SUMP TESTING <br />Test Method Developed By: ❑ Sump Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Spec) <br />Test Equipment Used: Incon Sump Tester Equipment Resolution: +/- 0.002" <br />Sump Diameter: <br />Sump Depth: <br />Sump Material: <br />Height from Tank Top to Top of <br />Highest Pi in Penetration: <br />Height from Tank Top to Lowest <br />Electrical Penetration: <br />Condition of sump prior to testing: <br />Portion of Sump Tested' <br />Does turbine shut down when <br />sump sensor detects liquid (both <br />product and water)?` <br />Turbine shutdown response time <br />Is system programmed for fail-safe <br />shutdown?' <br />Was fail-safe verified to be <br />Wait time between applying <br />pressure/vacuum/water and starting <br />test: <br />Test Start Time: <br />Initial Reading (R): <br />Test End Time: <br />Final Reading (RF): <br />Test Duration: <br />Change in Reading (RF -R,): <br />Pass/Fail Threshold or Criteria: <br />Test Result: <br />Was sensor removed for testing? <br />Was sensor properly replaced and <br />verified functional after testing? <br />STP Sump # 87-B <br />42" <br />31" <br />Fiberglass <br />12" <br />19" <br />Good <br />2" above piping <br />STP Sump # 89-B <br />42" <br />31" <br />Fiberglass <br />13" <br />19" <br />Good <br />2" above piping <br />STP Sump # 91-B <br />42" <br />31" <br />Fiberglass <br />13" <br />19" <br />Good <br />2" above piping <br />❑ Yes ❑ No U NA f O Yes ❑ No U NA I ❑ Yes ❑ No U NA <br />N/A <br />N/A <br />N/A <br />❑ Yes El No ® NA ( ❑ Yes ❑ No ® NA I ❑ Yes ❑ No ® NA <br />■ E M M SXR K . <br />30 minutes <br />+/- 0.002" <br />❑ Pass D Fail <br />❑YesONoDNA <br />❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No U NA <br />30 minutes <br />+/- 0.002" <br />❑ Pass 0 Fail <br />❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ® NA <br />30 minutes <br />+/- 0.002" <br />❑ Pass © Fail <br />❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No O NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />"Sensor functionality was not confirmed. This procedure is not part of the Secondary Containment testing scope of work". <br />87-8, 89-B, & 91-B — Failed, due to torn test boots. <br />.V K <br />' If the entire depth of the sump is not tested, specify how much was tested. If the answer to My of the questions indicated with an <br />asterisk(*) is "NO" or "NA", the entire sump must be tested. (See SWRCB LG -160) <br />