Laserfiche WebLink
STEP 8 <br />CCOMPLETE ❑ <br />BEAD EPDXY <br />HEAVILY ON ALL SEAMS <br />3600 DEGREES AROUND <br />FITTING BEFORE <br />CLEANUP <br />*'- PIPE CLAMP <br />SEAL YOUR FITTING <br />BODY TOGETHER. <br />Stick this assembly to the wall and apply a strong pressure to push the halves <br />together and against the wall. Epoxy should ooze from every seam and joint. Clean the <br />face of the fitting with acetone or equivalent and remove excess epoxy. You want the fit- <br />ting clean enough to remove the pipe clamp after the fitting cures. <br />Use provided pipe clamp to secure the fitting halves to each other. More epoxy may <br />ooze from the split seams as you tighten, re -clean as necessary. <br />LET THE FITTING CURE DO NOT ALLOW THE PIPE OR <br />CONDUITS TO MOVE OR TWIST DURING THE CURE STAGE <br />After a full cure, remove the pipe clamp holding the two fitting halves together. If it is <br />too difficult to remove and appears to be bonded in place, do not force it off. <br />STEP 9Water Testin : <br />CCOMPLETE ❑ <br />After the F -Series Retrofit -S Fittings are installed and have fully cured, water level test to a <br />minimum of 2" above the highest penetration fitting on the sump. Follow local regulations. <br />If this Retrofit was installed to steel sumps: <br />Re -coat and corrosion -protect any exposed steel around the fitting area. <br />0 13 6 i -F -Series -Retrofit -S-1 5A <br />