Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 7. UNDER-DISPENSER CONTAINMENT(UDQ TESTING <br /> Test Method Developed By: ❑UDC Manufacturer ®Industry Standard F1 Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum ®Hydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Incon Incon TS-STS Tester Equipment Resolution: +/-0.002" <br /> mmmmmmmmmmmm <br /> UDC# 13 UDC# 14-15 UDC# 16 UDC# <br /> UDC Manufacturer: Unknown Unknown Unknown <br /> UDC Material: Fiberglass Fiber lass Fiberglass <br /> UDC Depth: 30" 30" 30" <br /> Height from UDC Bottom to Top 12" 12" 10" <br /> of Highest Piping Penetration: <br /> Height from UDC Bottom to N/A N/A N/A <br /> Lowest Electrical Penetration: <br /> Condition of UDC prior to <br /> Dry Dry Dry <br /> testing: <br /> Portion of UDC Tested 16" 16" 15" <br /> Does turbine shut down when <br /> UDC sensor detects liquid(both ❑Yes ❑No k NA ❑Yes ❑No ®NA []Yes ❑No K NA ❑Yes ❑No ®NA <br /> product and water)?* <br /> Turbine shutdown response time <br /> Is system programmed for fail- ❑Yes []No k NA ❑Yes ❑No ®NA ❑Yes ❑No ®NA ❑Yes ❑No ®NA <br /> safe shutdown?* <br /> Was fail-safe verified to be ❑Yes ❑No k1NA ❑Yes ❑No ®NA ❑Yes ❑No ®NA ❑Yes ❑No ®NA <br /> o erational?* <br /> Wait time between applying <br /> pressure/vacuum/water and 15 minutes 15 minutes 15 minutes <br /> starting test <br /> Test Start Time: 2:45pm 3:01 pm 2:08pm 2:26pm 1:47pm 2:08pm <br /> Initial Reading (RI): 2.8551" 2.8546" 1.9652" 1.9665" 5.0565" 5.0552" <br /> Test End Time: 3:00pm 3:16pm 2:23 m 2:41 pm 2:02pm 2:23pm <br /> Final Reading RF): 2.8548" 2.8539" 1.9663" 1.9669" 5.0455" 5.0544" <br /> Test Duration: 15 Minutes Each 30 15 Minutes Each 30 15 Minutes Each 30 <br /> Change in Reading RF-RI : -0.0003 1 -0.0007 0.0011 0.0004 -0.011 -0.0008 <br /> Pass/Fail Threshold or Criteria: +/-0.002" +/-0.002" +/-0.002" +/-0.002 +/-0.002" +/-0.002" <br /> Test Result: 19 Pass ©.Fail K Pass 0 Fail 9 Pass 0 Fail 0 Pass0 Pail <br /> Was sensor removed for testing? ®Yes ❑No ❑NA ®Yes ❑No ❑NA 9 Yes ❑No ❑NA ❑Yes ❑No ®NA <br /> Was sensor properly replaced and k Yes ❑No ❑NA 9 Yes ❑No ❑NA 9 Yes ❑No ❑NA ❑Yes ❑No ®NA <br /> verified functional after testing? <br /> Comments—(include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> *Unable to test; UDC#1-2,#3-4,#5-6,#7-8,#9-10,#11-12,#17&17s,#18&18s,#19& 19s,#20&20s,#21 &21 s, <br /> #22 &22s,#23&23s,#24&24s,#25 &25s,#26&26s,#27&27s,#28&28s,#29&29s and#30&30s. Due to missing boots. <br /> 2 2 013 <br /> ENVIRONMENTAL <br /> 'If the entire depth of the UDC is not tested,specify how much was tested. If the answer to any of the questions indicated with an <br /> asterisk(*)is"NO"or"NA",the entire UDC must be tested. (See SWRCB LG-160) <br />