Laserfiche WebLink
SWRCB, January 2002 <br />5. PIPING SUMP TESTING <br />Page of <br />Does turbine shut down when <br />sump sensor detects liquid (both X Yes ❑ No NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br />product and water)?" <br />Turbine shutdown response time N/A <br />Is system programmed for fail-safe X Yes El No F]❑yes ❑ No ❑ NA ❑Yes ❑ No El NA ❑Yes ❑ No ❑ NA <br />shutdown?. NA <br />Was fail-safe verified to be X Yes ❑ No ❑ ❑ yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA ❑ Yes ❑ No ❑ NA <br />operational?' NA <br />Wait time between applying <br />pressure/vacuum/water and starting 30 minutes <br />test: <br />Test Start Time: <br />1:07/1:28 <br />Initial Reading (RI): <br />7.8119/7.8116 <br />Test End Time: <br />1:22/1:43 <br />Final Reading (RF): <br />7.8110/7.8108 <br />Test Duration: <br />15 min <br />Change in Reading (RF -RI): <br />-0.0009/-0.0008 <br />Pass/Fail Threshold or Criteria: <br />+/-0.002 <br />Test Result: <br />X Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />❑ Pass ❑ Fail <br />Was sensor removed for testing? <br />XYes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />Was sensor properly replaced and <br />verified functional after testing? <br />XYes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />❑ Yes ❑ No ❑ NA <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />Test boot installed. Removed after testing. <br />' If the entire depth of the sump is not tested, specify how much was tested. If the answer to as of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire sump must be tested. (See SWRCB LG -160) <br />