Laserfiche WebLink
Installation Guide TB1 Power inputs(ref.item 1,XFigure 9X) <br /> TB1 Power inputs (ref. item 1, Figure 9) <br /> Drive voltage should not exceed 230 Vac,±15%a. <br /> Table 12.Power Inputs-TB1 <br /> TBI Terminal I Input I Circuit Breaker Wire Sizes/Length Limits <br /> 0: 220,230,240 Vac Power <br /> L1 Hot (L1) #10 AWG 370 feet <br /> L2 Not used 20 Amp #12 AWG 236 feet <br /> L3 Hot (L2) <br /> Ground Stud Ground from power <br /> (item 3, Figure panel <br /> 9 on page 18) <br /> 0: 220,230,240 Vac Power <br /> L1 Phase 1 #10 AWG 683 feet <br /> #12 AWG 437 feet <br /> L2 Phase 2 15 Amp <br /> #14 AWG 275 feet <br /> L3 Phase 3 <br /> Ground Stud Ground from power <br /> (item 3, Figure panel <br /> 9 on page 18) <br /> Turn off, lock out,and tag power at the panel before making these connections. <br /> NOTE:VSFC Power Wire must be appropriate gauge shielded 4-conductor Anixter wire 14 AWG (2A-1404S <br /> or W2A-1404S), 12 AWG (2A- 1204S or W2A-1204S), 10 AWG (2A- 1004S or W2A-1004S), or CSA <br /> equivalent. <br /> 19 <br />