• Installation Guide TB2 Motor Wiring Outputs(ref.item 2,XFigure 9X) <br /> TB2 Motor Wiring Outputs (ref. item 2, Figure 9) <br /> Table 13.Motor Outputs-TB2 <br /> TB2 Terminal Motor Wire Color Acceptable Wire <br /> Sizes/Length Limits <br /> ANOTE: Power T1 Red wire <br /> in cable and Motor <br /> power out cable can T2 Orange wire #10 AWG 785 feet <br /> not be run in same <br /> conduit! T3 Black wire #12 AWG 502 feet <br /> #14 AWG 316 feet <br /> Ground Stud (item Blue wire <br /> 3, Figure 9 on page <br /> 18) <br /> Turn off, lock out,and tag power at the panel before making these connections. <br /> NOTE:VSFC Pump Wire must be appropriate gauge shielded 4-conductor Anixter wire 14 AWG <br /> (2A-1404S or W2A-1404S), 12 AWG(2A-1204S or W2A-1204S),10 AWG(2A- 10045 or W2A- <br /> 1004S),or CSA equivalent. <br /> NOTE: Both transducer and pump shielded cables must be sealed in accordance with NEC Article 501-5(d) <br /> which states that the outer jacket of multi-conductor cable must be removed within the seal off of the Division <br /> 1 location, (submersible sump) so the sealing compound will surround each individual conductor. Do not <br /> break the drain wire or remove any more of the jacket than is required. <br /> Before applying power to the VSFC unit,you must check the resistance between the <br /> terminals orf TB2:Resistances between terminals must be Within the ranges shown in Table 14. <br /> Table 14.Motor Wiring Resistance limits <br /> TB2 Terminals Resistance(Ohms) <br /> T1 -T2 2-3 ohms <br /> T2 -T3 2-3ohms <br /> T1 -T3 2 - 3 ohms <br /> i <br /> T1,T2,T3 to ground Infinite (at least 1 Megohm) <br /> NOTE:It is possible to wire the pump so that it runs in reverse.To verify correct rotation,temporarily <br /> disconnect the transducer wires.With the pump running at shutoff(no flow),the pressure should be 28 to 32 <br /> psi. If pressure is much lower, reverse any two of the motor wires at the TB2 terminal. <br /> 20 <br />