Laserfiche WebLink
TANKNOLOGY <br /> Stage II Vapor Recovery Test Results Form <br /> Air/Liquid Ratio Test For Vacuum Assist Systems <br /> Site Information: 7-ELEVEN#32262 2360 GRANTLINE I-205 OFF RAMP TRACY CA.95376 <br /> Work Order#: 2222223 Date: 05/15/2002 Technician: MICHAEL T LEVESQUE <br /> Product Flow Rate Calculation Air Volume Metered(ft^3) Ambient Conditions Corrected Final <br /> Gallons(g) Time(s) Flowrate Initial Final Volume Pressure Temp. Air Volume Calculated A/L Ratio Results <br /> Nozzle# Product Dispensed Seconds G.P.M. Reading Reading Metered Inches Hg Degrees F (ft13) A/L Average Pass/Fail <br /> 7.498 50.10 9.0 2947.99 2949.05 1.060 1.06 <br /> 9 opw 27r PREMIUM 1.06 Pass <br /> 7.510 49.25 9.1 2949.05 2950.10 1.050 1.05 <br /> 9 opw 27r PLUS 1.05 Pass <br /> 7.510 50.47 8.9 2950.10 2951.14 1.040 1.04 <br /> 10 opw 27r REG 1.04 Pass <br /> 7.503 50.00 9.0 2951.14 2952.16 1.020 1.02 <br /> 10 opw 27r PREMIUM 1.02 Pass <br /> 7.500 50.91 8.8 2952.16 2953.16 1.000 1.00 <br /> 10 opw 27r PLUS 1 1.00 Pass <br /> Type of System Tested: Gilbarco Vapory <br />