Laserfiche WebLink
TANKNOLOGY <br /> Stage II Vapor Recovery Test Results Form <br /> Air/Liquid Ratio Test For Vacuum Assist Systems <br /> Site Information: 7-ELEVEN#32262 2360 GRANTLINE I-205 OFF RAMP TRACY CA.95376 <br /> Work Order#: 2222223 Date: 05/15/2002 Technician: MICHAEL T LEVESQUE <br /> Product Flow Rate Calculation Air Volume Metered(f03) Ambient Conditions Corrected Final <br /> Gallons(g) Time(s) Flowrate Initial Final Volume Pressure Temp. Air Volumt Calculated A/L Ratio Results <br /> Nozzle# Product Dispensed Seconds G.P.M. Reading Reading Metered Inches Hg Degrees F (ft^3) A/L Average Pass/Fail <br /> 7.503 51.38 8.8 2942.66 2943.75 1.090 1.09 <br /> 7 opw 27r PLUS 1 1.09 Pass <br /> 7.513 48.18 9.4 2943.75 2944.82 1.070 1.07 <br /> 8 opw 27r REG 1.07 Pass <br /> 7.496 49.25 9.1 2944.82 2945.90 1.080 1.08 <br /> 8 opw 27r PREMIUM 1.08 Pass <br /> 7.501 50.18 9.0 2945.90 2946.96 1.060 1.06 <br /> 8 opw 27r PLUS 1.06 Pass <br /> 7.519 46.78 9.6 2946.96 2947.99 1.030 1.02 <br /> 9 opw 27r REG 1.02 Pass <br /> Type of System Tested: Gilbarco Vapory <br />