Laserfiche WebLink
Form 1 <br /> Source Test Tesults <br /> Static Leak Test <br /> Date: 05/15/2002 Time: 09:20 Application No. <br /> GDF Name and address: 32262 2360 GRANTLINE,I-205 OFF RAMP <br /> Stage II system(check one): Vapor Balance [ ] Single Hose M.P.D. [X ] <br /> Vacuum Assist [X ] Type: GILBARCO <br /> Stage I type(check one): Two point [X ] Manifolded? Yes [X ] <br /> Coaxial [ ] No [ ] <br /> Tank# 1 2 3 <br /> Product grade re ular plus premium <br /> Actual tank ca acit (gallons) 15040 10028 10028 35096 <br /> Gasoline volume(gallons) 8707 7028 5364 21099 <br /> Ullage(gallons) 6333 2894 4664 13891 <br /> Initial pressure of UST,inches H2O 2 2 <br /> Number of nozzles served by tank 12 12 <br /> Test location: (A) Stage I vapor <br /> coupler of(B)Stage II riser a <br /> Initial Pressure,inches H2O(2.0) 2 <br /> Pressure after 1 min. (inches H2O) 1.96 <br /> Pressure after 2 min. (inches H2O) 1.93 <br /> Pressure after 3 min. (inches H2O) 1,90 <br /> Pressure after 4 min. (inches H2O) 1.87 <br /> Final Pressure after 5 min. (inches <br /> H2O) 1.84 <br /> Allowable Final Pressure: Table 1A, <br /> Table 1B,Equations 9.1,9.2 1.92 <br /> Test Status [Pass or Fail] Fail <br /> Tests Conducted By: MLEVESQUE <br /> Test Company: TANKNOLOGY Date of Tests: 05/15/2002 <br /> Tests Witnessed By: none <br />