Laserfiche WebLink
0 <br /> WARNING:All internal piping must be at least 4"(6"for 12'diame- If the tank has a sump or a bottom fitting,take extra care that the <br /> ter tanks)from the tank bottom. tank does not rest on it prior to installation. ~ <br /> Refer to Figure 91 and Table 91 to determine the correct dimen- During installation,provide a clear area in the bedding material,so <br /> sions to size internal pumps and piping. that the tank rests on the bedding and the sump or bottom fitting is <br /> When the tank's interstitial space is filled with a liquid,the space clear.After setting the tank,fill and tamp the resulting void by hand <br /> must be vented.It is sufficient to drill a 1/4"-diameter hole in the before continuing the backfilling. <br /> side or cap of the monitor system riser pipe.When the ground- <br /> water level will be high enough to enter a drilled vent hole,install a <br /> separate vent line from the riser pipe to above grade level. When the tank has been set,tested and backfilled,and all piping <br /> When the interstitial space is dry,it is not necessary to vent the and venting has been completed,the balance of the backfill material <br /> space to atmosphere. may be added. <br /> It is the installers responsibility to select a thread sealant that is When the tank has been backfilled to subgrade,take the final <br /> compatible with the product being stored.Some sealants cannot diameter reading(Deflection reading"B on the checklist). <br /> be used with some products.If necessary,remove,clean and The same material as specified in Section 3 must be used to <br /> redope all plugs. completely fill excavation.The backfill must be free of debris.Any <br /> blocks or bricks used as support material during piping must be <br /> H removed prior to completion of backfilling.Safety measures,such <br /> ®-A g D _G as placing barricades until installation is complete;should be used <br /> DIMENSION LINE DETAIL DIMENSION LINE DETAIL around the excavation site. <br /> SINGLE WALL B DOUBLE WALL II DOUBLE NALL I <br /> SCALE, 1/16 SCALE. 1/16 Be sure that the installation meets all of the requirements of <br /> minimum cover as spedfied in Section 4. <br /> Be sure that the checklist is properly completed. <br /> •B• •E• <br /> .C, ,A, •F. ,D, •I• ,G, <br /> 1 s <br /> SINGLE WALL RIDOUBLE WALLBBED OUTER MALL DOE WALL <br /> I L DIPSTICK PREPARATION <br /> sMO <br /> Drive a small-headed,non-sparking(e.g. brass)nail into a wooden <br /> NOTE' I -ALL FITTING DIMENSIONS ARE MEASURED FROM THE TOP OF A dipstick at the 1"mark. <br /> SERVICE FITTING TO THE INSIDE BOTTOM OF THE TAN:AND <br /> INCLUDE GAUGE PLATE CLEARANCE. FIRST DIAMETER READING <br /> 2- INTERIOR DIAMETERS DO NOT INCLUDE GAUGE PLATE CLEARANCE. <br /> 1. Place the dipstick into a service fitting. <br /> FIGURE 91 2. Measure and record the distance from the tank bottom to the <br /> top of the fitting. <br /> TABLE 91 3. Pull the dipstick up until the nail catches on the inside top <br /> of the tank <br /> INTERIOR DIMENSIONS(IN) 4. Measure the distance from the tank top(inside)to the top <br /> TANK of the fitting.Subtract 1"from this measurement and record <br /> DIA. "A" "B" "C" "D" "E" I "P" "6" "H" "I" the distance. <br /> 4' 49.50 54.50 48.00 51.50 56.625 48.00 1 5. Subtract the second distance from the first and record this <br /> 6' 73.00 78.00 71.36 72.75 77.75 70.625 75.125 80.25 71.36 value as reading`A"on the Installation Checklist. <br /> SECOND DIAMETER READING <br /> 8' 93.00 98.00 91188 92.75 97.75 90.625 95.375 100.50 91188 <br /> 1. Place the dipstick into a service fitting with a riser installed <br /> 10' 121.00 126.00 11916 120.75 125.75 118.50 123.50 128.625 11916 to subgrade. <br /> 12' 138.25 143.25 136.625 2. Measure and record the distance from the tank bottom to the <br /> top of the standpipe. <br /> All piping must conform to all applicable codes and standards.See 3. Pull the dipstick up until the nail catches on the inside top of <br /> INTRODUCTION. the tank. <br /> WARNING:When pressure testing the piping,the tank must be 4. Measure the distance from the tank top(inside)to the top of <br /> isolated from the piping system.The test pressures for piping the standpipe.Subtract 1 from this measurement and record <br /> may cause the tank to explode and cause death,severe personal the distance. <br /> injury or property damage. 5. Subtract the second distance from the first and record this <br /> CAUTION:when extending monitoring or vapor recovery piping to the surtace,be value as reading"B"on the Installation Checklist. <br /> sure that the at-grade fittings are different from any fill fittings and will not accept _ <br /> standard fill hoses. <br />