Laserfiche WebLink
SWRCB,January 2002 Page of <br /> 5. SECONDARY PIPE TESTING <br /> Test Method Developed By: Piping Manufacturer x Industry Standard Professional Engineer <br /> Other(Specify) <br /> Test Method Used: x Pressure Vacuum Hydrostatic <br /> Other(Spec) <br /> Test Equipment Used:Pressure Test Gauge Equipment Resolution:+/-0.1 PSI <br /> SEMEMEMIE <br /> Piping Run#87 Piping Run#91 Piping Run#DSL Piping Run# <br /> Piping Material: Flex Flex FRP <br /> Piping Manufacturer: Western Fiberglass Western Fiberglass Ameron <br /> Piping Diameter: 2" 2" 4" <br /> Length of Piping Run: 485' 485' 240' <br /> Product Stored: Unleaded Premium Diesel <br /> Method and location of Test Boot Test Boot Test Boot <br /> piping-run isolation: <br /> Wait time between applying <br /> pressure/vacuum/water and 15 Minutes 15 Minutes 15 Minutes <br /> starting test: <br /> Test Start Time: 5:00 pm 5:00 pm 5:00 pm <br /> Initial Reading(R,): `5 PSI 5 PSI 5 PSI <br /> Test End Time: 6:00 pm 6:00 pm 6:00 pm <br /> Final Reading(RF): 5 PSI 5 PSI 5 PSI <br /> Test Duration: 1 Hour 1 Hour 1 Hour <br /> Change in Reading(RF-R,): 0 0 0 <br /> Pass/Fail Threshold or +/-0.2 PSI +/-0.2 PSI +/-0.2 PSI <br /> Criteria: <br /> est Result: x Pass C1 Fail x Pass ❑Fail x Pass ❑Pail 0 Pass 0 Fail <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> We replaced the 87 test boot in dispenser #15/16. <br /> We replaced the 91 test boot in dispenser #13. <br /> We replaced the diesel test boot in stp #3. <br />