E <br />SWRCB, January 2002 <br />Page 5 of 7 <br />7. UNDER -DISPENSER CONTAINMENT UDC TESTING <br />Test Method Developed By: ❑ UDC Manufacturer ® Industry Standard ❑ Professional Engineer <br />❑ Other (Specify) <br />Test Method Used: ❑ Pressure ❑ vacuum ® Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used:Incon TS -STS Equipment Resolution:+/ -0.0001" <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />' If the entire depth of the UDC is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160) <br />UDC #24 Main <br />UDC #24 Sat <br />UDC #25 Main <br />11 KENN= <br />UDC #25 Sat <br />UDC Manufacturer: <br />Western Fiberglass <br />Western Fiberglass <br />Western Fiberglass <br />Western Fiberglass <br />UDC Material: <br />FRP <br />FRP <br />FRP <br />FRP <br />UDC Depth: <br />31" <br />31" <br />31" <br />31" <br />Height from UDC Bottom to Top <br />9" <br />9" <br />9" <br />9" <br />of Highest Piping Penetration: <br />Height from UDC Bottom to <br />6" <br />6" <br />6" <br />6" <br />Lowest Electrical Penetration: <br />Condition of UDC prior to <br />OK <br />OK <br />OK <br />OK <br />testing: <br />Portion of UDC Tested <br />2"above highest Pipe pen <br />2"above highest Pipe pen <br />2"above highest Pipe pen <br />2"above highest Pipe pen <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />❑Yes [:]No ®NA <br />❑Yes ❑No ®NA <br />[-]Yes ❑No ®NA <br />❑Yes ❑No ®NA <br />product and water)?* <br />Turbine shutdown response time <br />N/A <br />N/A <br />N/A <br />N/A <br />Is system programmed for fail- <br />❑Yes ❑No ®NA <br />❑Yes ❑No ®NA <br />❑Yes ❑No ®NA <br />❑Yes ❑No ®NA <br />safe shutdown?` <br />Was fail-safe verified to be <br />[-]Yes ❑No ®NA <br />[:]Yes❑No ®NA <br />❑Yes ❑No ®NA <br />❑Yes ❑No ®NA <br />o erational?* <br />Wait time between applying <br />pressure/vacuum/water and <br />15 Minutes <br />15 Minutes <br />15 Minutes <br />15 Minutes <br />starting test <br />Test Start Time: <br />10:55 11:14 <br />10:55 11:14 <br />2:01 2:17 <br />2:01 <br />2:17 <br />Initial Reading (Ri): <br />6.4787 6.4787 <br />2.8627 2.8629 <br />4.2320 4.2317 <br />4.2106 <br />4.2108 <br />Test End Time: <br />11:10 11:29 <br />11:10 11:29 <br />2:16 2:32 <br />2:16 <br />2:32 <br />Final Reading (RF): <br />6.4787 6.4788 <br />2.8630 2.8630 <br />4.2319 4.2317 <br />4.2107 <br />4.2107 <br />Test Duration: <br />15 Min Each (30 Min) <br />15 Min Each (30 Min <br />15 Min Each (30 Min) <br />15 Min Each (30 Min <br />Change in Reading (RF -RI): <br />0.0000 1 0.0001 <br />0.0003 1 0.0001 <br />0.0001 1 0.0000 <br />0.0001 1 0.0001 <br />Pass/Fail Threshold or Criteria: <br />+/- 0.002" <br />+/- 0.002" <br />+/- 0.002" <br />+/- 0.002" <br />Test Result: <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />Was sensor removed for testing? <br />_ffYes No NA <br />ZYes 0No NA <br />®Yes No ❑NA <br />®Yes No [-INA <br />Was sensor properly replaced and <br />®Yes ❑No [INA®Yes <br />❑No El <br />®Yes ❑No ❑NA <br />®Yes ❑No ❑NA <br />verified functional after testin Y <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />' If the entire depth of the UDC is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160) <br />