Laserfiche WebLink
SWRCB, January 2002 <br />7. UNDER -DISPENSER CONTAINMENT (UDC) TESTING <br />Page 5 of 7 <br />Test Method Developed By: ❑ UDC Manufacturer N Industry Standard ❑ Professional Engineer <br />❑ Other (Spec) <br />Test Method Used: ❑ Pressure ❑ Vacuum ® Hydrostatic <br />❑ Other (Specify) <br />Test Equipment Used:Incon TS -STS Equipment Resolution:+/ -0.0001" <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />1 If the entire depth of the UDC is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160) <br />UDC #26 Main <br />UDC #26 Sat <br />UDC #27 Main <br />UDC 927 Sat <br />UDC Manufacturer: <br />Western Fiberglass <br />Western Fiberglass <br />Western Fiberglass <br />Western Fiberglass <br />UDC Material: <br />FRP <br />FRP <br />FRP <br />FRP <br />UDC De the <br />31" <br />31" <br />31" <br />31" <br />Height from UDC Bottom to Top <br />9" <br />9" <br />9" <br />9" <br />of Highest Piping Penetration: <br />Height from UDC Bottom to <br />6" <br />6" <br />6" <br />6" <br />Lowest Electrical Penetration: <br />Condition of UDC prior to <br />OK <br />OK <br />OK <br />OK <br />testing: <br />Portion of UDC Tested <br />2"above highest Pipe pen <br />2"above highest Pipe pen <br />2"above highest Pipe pen <br />2"above highest Pipe pen <br />Does turbine shut down when <br />UDC sensor detects liquid (both <br />❑Yes [:]No ®NA <br />❑Yes [:]No ®NA <br />❑Yes [:]No ®NA <br />❑Yes ❑No ®NA <br />product and water)?` <br />Turbine shutdown response time <br />N/A <br />N/A <br />N/A <br />N/A <br />Is system programmed for fail- <br />❑Yes ❑No ®NA <br />❑Yes ❑No ®NA <br />[:]Yes❑No ®NA <br />[:]Yes[—]No ®NA <br />safe shutdown?' <br />Was fail-safe verified to be❑Yes <br />[-]No ®NA <br />Y❑es N❑o NA <br />® <br />Yes <br />❑ ❑No ®NA <br />❑Yes ❑No ®NA <br />operational?* <br />Wait time between applying <br />pressure/vacuum/water and <br />15 Minutes <br />15 Minutes <br />15 Minutes <br />15 Minutes <br />starting test <br />Test Start Time: <br />2:01 2:17 <br />2:45 3:01 <br />2:45 3:01 <br />3:01 3:18 <br />Initial Reading (RI): <br />4.6325 4.6330 <br />3.5651 3.5650 <br />4.7942 4.7939 <br />3.7267 3.7267 <br />Test End Time: <br />2:16 2:32 <br />3:00 3:16 <br />3:00 3:16 <br />3:16 3:33 <br />Final Reading (RF): <br />4.6330 4.6328 <br />3.5649 3.5649 <br />4.7939 4.7939 <br />3.7265 3.7266 <br />Test Duration: <br />15 Min Each (30 Min) <br />15 Min Each (30 Min <br />15 Min Each 30 Min <br />15 Min Each 30 Min) <br />Change in Reading (RF -RI): <br />070-0-0-5-1 0.0002 <br />0.0002 1 0.0001 <br />0.0003 1 0.0000 <br />0.0002 1 0.0001 <br />Pass/Fail Threshold or Criteria: <br />+/- 0.002" <br />+/- 0.002" <br />+/- 0.002" <br />+/- 0.002" <br />Test Result: <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />® Pass ❑ Fail <br />M Pass ❑ Fail <br />Was sensor removed for testing? <br />Yes [-]No NA <br />ZYes ❑No NA <br />ZYes ❑No NA <br />®Yes No NA <br />Was sensor properly replaced and <br />®Yes ❑No ❑NA <br />®Yes ❑No ❑NA <br />®Yes ❑No ❑NA <br />®Yes ❑No ❑NA <br />verified functional after testing? <br />Comments — (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br />1 If the entire depth of the UDC is not tested, specify how much was tested. If the answer to any of the questions indicated with an <br />asterisk (*) is "NO" or "NA", the entire UDC must be tested. (See SWRCB LG -160) <br />