S WRCB,January 2002 Page of <br /> 8. FILL RISER CONTAINMENT SUMP TESTING <br /> Facility is Not Equipped With Fill Riser Containment Sums ❑ <br /> Fill Riser Containment Sumps are Present,but were Not Tested ❑ <br /> Test Method Developed By: ❑Sump Manufacturer ,ixj„Industry Standard ❑Professional Engineer <br /> ❑Other(Spec) <br /> Test Method Used: ❑Pressure ❑Vacuum 004ydrostatic <br /> ❑Other(Spec) <br /> Test Equipment Used: Equipment Resolution: <br /> Fill Sume# Lt Fill S imp# Fill Sump# Fill Sume# <br /> Sump Diameter: t " <br /> Height from Tank Top to Top of ®� e <br /> Highest Piping Penetration: <br /> Height from Tank Top to Lowest c7"J ( <br /> Electrical Penetration: <br /> Condition of sump prior to <br /> testing: <br /> Portion of Sump Tested <br /> Sump Material: <br /> Wait time between applying Gl/ C7 <br /> pressure/vacuum/water and <br /> starting test: <br /> Test Start Time: <br /> Initial Reading(RI): <br /> Test End Time: l Z,•at <br /> Final Reading(RF): <br /> Test Duration: <br /> Change in Reading(RF-R,): Q <br /> Pass/Fail Threshold or Criteria: <br /> Test Result: XPass ❑Fail J&Pass ❑Fail krPass ❑Fail ❑ Pass ❑Fail <br /> Is there a sensor in the sump? es ❑No es ❑No es ❑No ❑Yes ❑No <br /> Does the sensor alarm when <br /> either product or water is ,8(Ves ❑No ❑NA KYes ❑No ❑NA <Yes ❑No ❑NA ❑Yes ❑No ❑NA <br /> detected? <br /> Was sensor removed for testing? , Yes ❑No ❑NA XYes ❑No ❑NA es ❑No ❑NA ❑Yes u No NA <br /> Was sensor properly replaced and yes ❑No ❑NA 'Yes ElNo El NA , 'Yes ❑No El =Yes NA ❑NA <br /> verified functional after test in ? <br /> Comments— (include information on repairs made prior to testing, and recommended follow-up for failed tests) <br /> t <br />