Page 17 FE 382- 063-00 <br /> Enqineered Filly The on-site soils are predominantly silty <br /> sands intermixed with debris such as trash , glass , etc. These <br /> soils will not be suitable for use as engineered fill . Import <br /> fill soil should be nonexpansive granular material and , prior to <br /> ' use , should be approved by the Soils Engineer. ; <br /> Fill soil should be placed in lifts approximately 6 inches <br /> thick , moisture- conditioned as necessary , and compacted to <br /> achieve a dry density of at least 95 percent of the maximum dry <br /> density As determined by ASTM Test Method D1557-78. Additional <br /> lifts should not be placed if the previous lift did n.ot meet the <br /> required dry density or if soil conditions are not stable. <br /> Utility Trench Backfill : Utility trench backfill placed in <br /> _ v r ad j ae en t to building areas and paved exterior slabs should be <br /> >: compacted to at least 95 percent relative compaction based on <br /> ASTM Test Method D1557- 78 . When utility trench backfills are <br /> deemed nonstru.ctural backfills as determined by the Soils <br /> Engineer , the surface 2 feet of fill should be compacted to -at <br /> least 95 percent relative compaction, and fill material below the <br /> surface. 2 feet should be compacted to 90 percent relative <br /> compaction. The. Contractor should use appropriate equipment and <br /> methods to avoid damage to the. utilities and/or structures during <br /> placement and compaction of the backfill material. <br /> The Found,don En,._neeers, Inc. <br />