Laserfiche WebLink
FOURTH QUARTER 2006 GROUNDWATER TREATMENT FACILITY MONITORING REPORT <br /> FORWARD LANDFILL WDR ORDER NO.R5-2003-0080 <br /> conveyance pipe adjacent to the wet area in the access road.The wet area was marked with <br /> a stake and flagging tape.The CV Water Board was informed of the leak via e-mail on <br /> December 20,2006 (Atkinson,2006). <br /> EW-1 and the GTF continued to operate until the end of fourth quarter 2006. Repairs to the <br /> groundwater conveyance pipeline are scheduled for the week of January 8,2007. Following <br /> the repairs,EW-2 will be restarted and the repaired pipe will be thoroughly examined for <br /> leaks.After the pipeline is successfully repaired,EW-2 and the GTF will be returned to <br /> normal operation during first quarter 2007. <br /> The GTF hour meter failed during fourth quarter 2006 and will be repaired or replaced <br /> during first quarter 2007. <br /> 3.0 Influent and Effluent Monitoring <br /> Under WDR Order No. R5-2003-0080, effluent samples are analyzed as follows: <br /> • Monthly for pH,specific conductivity, and VOCs <br /> • Quarterly for total dissolved solids <br /> • Annually for dissolved inorganics <br /> All parameters were analyzed during fourth quarter 2006. Figure 1 shows the effluent <br /> monitoring location. Table 2 presents the results of the effluent monitoring performed <br /> during fourth quarter 2006. Appendix A contains the effluent monitoring field sampling <br /> logs and laboratory results for fourth quarter 2006. <br /> The current WDRs stipulate that the concentration limit for VOCs in the effluent is <br /> nondetect. No VOCs were detected in the GTF effluent samples collected during fourth <br /> quarter 2006. <br /> Under WDR Order No.R5-2003-0080,influent sampling for pH,specific conductivity, <br /> turbidity, and VOCs are performed semiannually. Influent samples are collected from a <br /> sample port in the header pipe adjacent to the air stripper.Semiannual influent monitoring <br /> was conducted on November 16,2006. Table 3 presents the results of the influent monitor- <br /> ing performed during fourth quarter 2006. Appendix A contains the influent monitoring <br /> field sampling logs and laboratory results for fourth quarter 2006. <br /> As required by the current WDRs,historical influent and effluent analytical results (detected <br /> analytes only) are tabulated on a compact disc in Appendix B. Appendix B also contains <br /> historical influent and effluent pH and conductivity data. The Appendix B data cover the <br /> period from August 1994 to December 2006. The results are drawn from a CH2M HILL <br /> database and historical reports. <br /> During first quarter 2007, effluent samples will be collected monthly and analyzed for pH, <br /> specific conductivity,and VOCs.One quarterly effluent sample will be analyzed for total <br /> dissolved solids. Influent samples will again be collected during second quarter 2007. <br /> RDD/070170002(NLH3358.DOC) 3 <br />