t <br /> cYnical Data (at genset) <br /> Data at: Full Part Load <br /> load <br /> Fuel gas LHV BTU/scft 319 <br /> 100% 75% 50% <br /> Energy input MBTU/hr 2 18,033 13,976 9,919 <br /> Gas volume scfhr 56,530 43,812 31,094 <br /> Mechanical output bhp 1 3,012 2,258 1,506 <br /> Electrical output kw el. 4 2,175 1,625 1,075 <br /> Heat to be dissipated 5 <br /> Intercooler 1st stage (Engine jacket water cooling circuit MBTU/hr 1,355 <br /> Intercooler 2nd stage (Engine jacket water cooling MBTU/hr 163 <br /> circuit <br /> Lube oil (with gearbox) (Engine jacket water cooling MBTU/hr 898 <br /> circuit <br /> Jacket water MBTU/hr 1,300 <br /> Surface heat ca. MBTU/hr [71 438 <br /> Balance heat MBTU/hr 181 <br /> Spec. fuel consumption of engine BTU/bh .hr H21 5,987 61189 6,587 <br /> Lube oil consumption ca. al/hr 1[31 0.21 <br /> Electrical efficiency % 41.1% 39.7% 37.0% <br /> ')approximate value for pipework dimensioning <br /> U Explanations:see 0.10-Technical parameters <br /> All heat data is based on standard conditions according to attachment 0.10. Deviations from the standard conditions can result in a <br /> change of values within the heat balance,and must be taken into consideration in the layout of the cooling circuit/equipment <br /> (intercooler;emergency cooling;...). In the specifications in addition to the general tolerance of+/-8%on the thermal output a <br /> further reserve of 10%is recommended for the dimensioning of the cooling requirements. <br /> CH4>50 Vol.%required for specified NCx-emissions <br /> 19.04.2011/2 TS JGS616 E22 4160V April 19 2011 Ameresco Forward LFG-WES <br /> 4/32 <br />