Laserfiche WebLink
TABLE 12A <br /> CONCEPTUAL GROUNDWATER EXTRACTION AND AIR STRIPPER DESIGN SUMMARY <br /> CORRAL HOLLOW SANITARY LANDFILL ENGINEERING FEASIBILITY STUDY <br /> Parameter Point of Compliance <br /> Spacing between wells(ft) 100 <br /> Total number 9 <br /> Diameter of wells(inches) 4 <br /> Extraction Pump,maximum gpm,each 10 <br /> Total depth of wells(ft.) 105 <br /> Total Dynamic Head(TDH) 110 <br /> Extraction Pump(HP)each 1 <br /> No.of compressors 3 <br /> Compressor capacity(scfm) 16 <br /> Compressor HP 7.5 <br /> Aboveground piping,extraction system,total(ft) 950 <br /> Aboveground storage(10,000 gallons) 1 <br /> Effluent discharge pump(gpm) 9 <br /> No.of Pumps 1 <br /> Pump HP 5 <br /> Diameter of conveyance piping to existing air stripper 4-in HDPE <br /> Length of conveyance piping to air stripper(ft.) 950 <br /> Length of Corrugated HDPE air stripper pipeline(ft.) 500 <br /> Diameter of Corrugated HDPE air stripper pipeline 24-inches <br /> Vapor Phase GAC treatment system 1 <br />