• Examine the joint when the pipe is released from the fusion welding machine to verify <br /> that the weld is completely around the entire circumference of the pipe. <br /> 5.2.3 Flanged Connections Installation <br /> • Verify that polyethylene flanges are at the same temperature of the surrounding backfill <br /> soil at the time the flanges are bolted to prevent relaxation of the flange bolts and loosing <br /> of the joint due to thermal contraction of the polyethylene material. Verify that the flange <br /> bolts are re-tightened 24-hours after the flange bolts were initially tightened. <br /> Page 40 <br />