Laserfiche WebLink
Recommended Practices for the Testing and Verification of Spill,Overfill,Leak Detection and Secondary Containment Equipment at UST Facilities <br /> TABLE 9-1. <br /> VOLUME THAT MUST BE DISCHARGED <br /> WITHIN THE INDICATED TIME FRAME TO BE EQUIVALENT <br /> TO A LEAK RATE OF 3 GPH AT 10 PSIG. <br /> Line Pressure 15 seconds 60 seconds <br /> 8 psig 42 ml 169 ml <br /> 9 psig 45 ml 179 ml <br /> 10 psig 47 ml 189 ml <br /> 11 psig 50 ml 198 ml <br /> 12 psig 52 ml 207 ml <br /> 13 psig 54 ml 216 ml <br /> 14 psig 56 ml 224 ml <br /> 15 psig 58 ml 232 ml <br /> 16 psig 60 ml 239 ml <br /> 17 psig 62 ml 247 ml <br /> 18 psig 64 ml 254 ml <br /> 19 psig 65 ml 261 ml <br /> 20 psig 67 ml 268 ml <br /> 21 psig 69 ml 274 ml <br /> 22 psig 70 ml 281 ml, <br /> 23 psig 72 ml 287 ml <br /> 24 psig 73 ml 293 ml <br /> 25 psig 75 ml 299 ml <br /> 26 psig 76 ml 305 ml <br /> 27 psig 78 ml 311 ml <br /> 28 psig 79 ml 317 ml <br /> 29 psig 81 ml 322 ml <br /> 30 psig 82 ml 328 ml <br /> 31 psig 83 ml 333 ml <br /> 32 psig 85 ml 338 ml <br /> 33 psig 86 ml 344 ml <br /> 34 psig 87 ml 349 ml <br /> 35 psig 89 ml 354 ml <br /> 36 psig 90 ml 359 ml <br /> 37 psig 91 ml 364 ml <br /> 38 psig 92 ml 369 ml <br /> 39 psig 94 ml 374 ml <br /> 40 psig 95 ml 378 ml <br /> 41 psig 96 ml 383 ml <br /> 42 psig 97 ml 388 ml <br /> 43 psig 98 ml 392 ml <br /> 44 psig 99 ml 397 ml <br /> 45 psig 100 ml 401 ml <br /> 46 psig 102 ml 406 ml <br /> 47 psig 103 ml 410 ml <br /> 48 psig 104 ml 415 ml <br /> 49 psig 105 ml 419 ml <br /> 50 psig 106 ml 423 ml <br /> Adjust size of test apparatus leak orlflce untll the Indicated flow rate Is achieved. <br /> pei.org <br />