Laserfiche WebLink
Electronic Leak Detector Test Data Sheet <br /> Site Name Lodi CA FO Term ( Intl ) Date 03/05/20 <br /> Address 2500 West Turner Road <br /> Lodi CA 95242 <br /> Test Information <br /> 1 2 3 4 a <br /> Product Diesel <br /> Manufacturer Incon <br /> Model TS -LSU 500 <br /> Full Operating Pressure ( PSI) 26 psi <br /> F / E Holding Pressure (PSI) 22 psi <br /> Did Alarm sound with 3GP1 I lest . YES <br /> I low many turbine cycles before alarm. 2 cycles <br /> Is turbine shut down when in alarm . NO <br /> Test Leak Rate ( ml / rmin) (gph) 189 ml . <br /> PASS or FAIL PASS <br /> Comments : <br /> This letter certifies that the annual leak detector tests were performed at the above referenced <br /> facility according to the equipment manufacturers procedures and limitations and the results <br /> as listed are to my knowledge true and correct . The mechanical leak detector test pass / fail <br /> is determined using a low flow threshold trip rate of 3 gph at 10 PSI . <br /> Inspected By : Contractor sunwest engineering inc . <br /> Technician Ruben Becerra Lic# 1655 <br /> IRuben Becerra Digitally signed by Ruben Becerra <br /> Signature Date : 2020 . 03 . 05 10 : 22 : 53 <br />