My WebLink
|
Help
|
About
|
Sign Out
Home
Browse
Search
COMPLIANCE INFO_2020
Environmental Health - Public
>
EHD Program Facility Records by Street Name
>
E
>
EL DORADO
>
1605
>
2300 - Underground Storage Tank Program
>
PR0504388
>
COMPLIANCE INFO_2020
Metadata
Thumbnails
Annotations
Entry Properties
Last modified
3/8/2021 10:00:08 AM
Creation date
7/7/2020 3:29:03 PM
Metadata
Fields
Template:
EHD - Public
ProgramCode
2300 - Underground Storage Tank Program
File Section
COMPLIANCE INFO
FileName_PostFix
2020
RECORD_ID
PR0504388
PE
2361
FACILITY_ID
FA0006185
FACILITY_NAME
El Dorado Gas & Mart
STREET_NUMBER
1605
Direction
S
STREET_NAME
EL DORADO
STREET_TYPE
ST
City
STOCKTON
Zip
95206
APN
16703101
CURRENT_STATUS
01
SITE_LOCATION
1605 S EL DORADO ST
P_LOCATION
01
P_DISTRICT
001
QC Status
Approved
Scanner
SJGOV\kblackwell
Tags
EHD - Public
There are no annotations on this page.
Document management portal powered by Laserfiche WebLink 9 © 1998-2015
Laserfiche.
All rights reserved.
/
110
PDF
Print
Pages to print
Enter page numbers and/or page ranges separated by commas. For example, 1,3,5-12.
After downloading, print the document using a PDF reader (e.g. Adobe Reader).
View images
View plain text
Environmental Health DepartmentUnderground Storage Tank Program Inspection ReportDate:May 28, 2020Facility Address:1605 S EL DORADO ST, STOCKTONFacility Name:El Dorado Gas & MartSUMMARY OF VIOLATIONS(CLASS I, CLASS II, or MINOR - Notice to Comply)RemarksItem #201CCR 2712(b)(1-2) Failure to maintain monitoring, maintenance, and follow up action records. OBSERVATION: Maintenance and monitoring records for the last three years were not found on site. - The 2019 monitoring system certification test results were not found on site- The 2018 monitoring system certification test results were not found on site- The 2017 monitoring system certification test results were not found on site- The 5/31/2019 overfill prevention test results were not found on site.REGULATION GUIDANCE: These records shall be maintained on site for at least three years. Monitoring records include: (1) date and time of all monitoring or sampling; (2) monitoring equipment calibration and maintenance records; (3) results of any visual observations; (4) results of sample analysis performed a lab or in the field; (5) logs of all readings of gauges or other monitoring equipment, ground water elevations, or other test results; (6) results of inventory readings and reconciliations. CORRECTIVE ACTION: Immediately locate and maintain all missing maintenance and monitoring records for the last three years on site and submit copies to the EHD.This is a minor violation.202CCR 2715(c)(3), 2715(c)(4) Failure to maintain the "Facility Employee Training Certificate" on-site (after October 1, 2018). OBSERVATION: The Facility Employee Training Certificate dated 6/14/2019 did not have date of assuming responsibility as a facility employee. REGULATION GUIDANCE: All site employees must be trained prior to taking responsibility as a facility employee if after October 1, 2018, or within 30 days of hire if prior to October 1, 2018. The Facility Employee Training Certificate shall contain accurate information for all employees trained. CORRECTIVE ACTION: Update the Facility Employee Training Certificate to contain the accurate information and submit a copy of the updated form to the EHD.This is a minor violation.209CCR 2716(a-e) Failure to conduct the designated UST operator visual inspection at least once every 30 days. OBSERVATION: The designated operator failed to check and note all required items on the visual inspection reports. The incorrect and missing information included the following from the inspection reports:-The DO report of 11/14/2019 did not include the owner/operator name, signature and date signed.REGULATION GUIDANCE: During the visual inspection, the designated operator shall check that all required testing and maintenance for the UST system have been completed and shall check all required items on the report. CORRECTIVE ACTION: Ensure that designated operators performing visual inspections at this facility are including all of the required information on the reports.This is a minor violation.FA0006185 PR0504388 SC001 05/28/2020EHD 23-01 Rev. 9/20/2019Underground Storage Tank Program OIRPage 5 of 71868 E. Hazelton Avenue | Stockton, California 95205 | T 209 468-3420 | F 209 464-0138 | www.sjcehd.com
The URL can be used to link to this page
Your browser does not support the video tag.